2006-12-01 15:24:59*** DENIED ***
 1) NEED TO SHOW THE SIZE OF ALL DUCTS ON PLANS.
  
 2) NEED TO SHOW THE CFM'S. AT EACH AUPPLY AIR GRILL ON
 PLANS.
  
 3) SHOW ON PLANS HOW RETURN AIR IS GETTING BACK TO AIR
 HANDLER.
  
 4) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 5) IS 800/806 ONE UNIT WITH ONE A/C SYSTEM, OR TWO
 UNITS WITH TWO A/C SYSTEMS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.