Plan Review Notes For Permit 06110857 |
Permit Number |
06110857 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-12-08 11:37:00 | *** DENIED *** | | 1) ENERGY CALCULATIONS ARE SHOWING THE WRONG | | JURISDICTION NUMBER, PLEASE CORRECT. | | | | 2) ENERGY CAL'S. ARE CALLING FOR A HEAT PUMP UNIT, | | PLANS ARE CALLING FOR A STRAIGHT COOLING UNIT WITH | | ELECTRIC HEAT, PLEASE CORRECT ENERGY CAL'S. | | | | 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 4) PLEASE SUBMIT A COMPLETE ENERGY CALCULATION NOT JUST | | THE FRONT PAGE. | | | | 5) PLEASESUBMITMANUAL J CALCULATIONS, PER 2004 FBC | | 13-607.1.ABC.1 . | | | | 6) SHOW THE LOCATION OF THE CLOTHES DRYER VENT | | TERMINATION ON THE MECH. PLANS, BE AWARE THE VENT MAY | | NOT TERMINATE NEAR THE A/C CONDENSER UNIT, PER 2004 | | FBC/M 501.2 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|