Date |
Text |
2006-12-06 10:52:04 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS, FBC-2004 BUILDING, |
| NFPA-2004 CHAPTER 58 AND FLORIDA STATE STATUTES |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. THE SUBMITTED DRAWINGS ACCORDING TO THE TITLE BLOCK |
| ARE FROM THE ARCHITECTURE/ENGINEERING FIRM OF SPILLAS |
| CANDELA & PARTNERS INC. FLORIDA LICENSE NO. AAC000025 |
| AND THE ARCHITECT OF RECORD IS ANA B. VALDES, A/A FLA. |
| REG. NO. 11602. PER STATE STATUTES ARCHITECTURE CHAPTER |
| 481, FLORIDA STATUTES, PART 1 AND ENGINEERING CHAPTER |
| 481, ONLY THE ABOVE SAID FIRM AND ARCHITECT OF RECORD |
| CAN MAKE CHANGES TO THE SUBMITTED DRAWING AND THE |
| DRAWINGS MUST BE SIGNED AND SEALED BY THE ABOVE SAID |
| ARCHITECT OF RECORD. |
| |
| 2. PLEASE SUBMIT A DETAIL OF THE PROPANE EXCHANGE |
| CABINETS INDICATING THE SIZE AND MATERIAL TYPE PER |
| NFPA-2004 CHAPTER 58 SECTION 6.16.5.2. |
| |
| 3. PLEASE SUBMIT A DETAIL ON HOW PROPANE EXCHANGE |
| CABINETS ARE TO BE ANCHORED TO MEET 140MPH WIND LOAD |
| PER FBC-2004 BUILDING CHAPTER 16, SECTION 1603.1.4 WIND |
| DESIGN DATA AND SECTION 1609.1.3 ANCHORAGE AGAINST |
| OVERTURNING, UPLIFT AND SLIDING. |
| |
| 4. PLEASE INDICATE ON THE RESUBMITTED DRAWINGS FIRE |
| PROTECTION PER NFPA-2004 CHAPTER 58, SECTION 8.5. |
| |
| 5. PLEASE RESUBMIT A LEGIBLE COPY OF THE STATE OF |
| FLORIDA BUREAU OF LP GAS INSPECTION APPROVAL OF THE |
| PROPANE EXCHANGE CABINETS. |
| |
| 6. PLEASE INDICATE ON THE RESUBMITTED DRAWINGS |
| PROTECTION OF CYLINERS PER NFPA-2004 CHAPTER 58, |
| SECTION 8.4.2 AND SECTION 8.4.2.2. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |