2006-11-29 07:48:59DENIED BY BUILDING
  
 1) THE NOA FOR THE MODIFIED ROOF SYSTEM HAS A MAXIMUM
 DESIGN PRESSURE OF -52.5 PSF. ENHANCED FASTENING IS
 REQUIRED IN THE PERIMETER AND CORNER AREAS USING RAS
 117 CALCULATIONS. LIMITATION NUMBER 7 OF THE NOA
 REQUIRES THAT THESE CALCULATIONS BE PREPARED, SIGNED
 AND SEALED BY A FL REGISTERED ENGINEER, ARCHITECT OR
 REGISTERED ROOFING CONSULANT. PLEASE SUBMIT THE SIGNED
 AND SEALED RAS 117 CALCULATIONS.
  