Date Text
2006-12-22 18:20:43 
 PROVISO
  
 WHERE THE SERVICE FROM ONE BUILDING IS FEEDING THE PUMP
 DISCONNECT FOR ANOTHER BUILDING, CONNECTED TO A
 DIFFERENT SERVICE, DO NOT MOUNT THE DISCONNECT TO THAT
 STRUCTURE. M9OUNT AT PUMP LOCATION.
 LOCATE A PLAQUE PER 225.37 AT THE DISCONNECT.
  
 225.37 IDENTIFICATION.
 WHERE A BUILDING OR STRUCTURE HAS ANY COMBINATION OF
 FEEDERS, BRANCH CIRCUITS, OR SERVICES PASSING THROUGH
 IT OR SUPPLYING IT, A PERMANENT PLAQUE OR DIRECTORY
 SHALL BE INSTALLED AT EACH FEEDER AND BRANCH-CIRCUIT
 DISCONNECT LOCATION DENOTING ALL OTHER SERVICES,
 FEEDERS, OR BRANCH CIRCUITS SUPPLYING THAT BUILDING OR
 STRUCTURE OR PASSING THROUGH THAT BUILDING OR STRUCTURE
 AND THE AREA SERVED BY EACH.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.