Plan Review Notes For Permit 06110802 |
Permit Number |
06110802 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-12-26 11:10:08 | DENIED | | REFERENCE: FBC-2004 PLUMBING AND FBC-2004 | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | PLAN REVIEW: | | | | 1. PLEASE PROVIDE A DETAIL INDICATING BOOSTER PUMP | | LOCATION TO STRUCTURES AND HOW BOOSTER PUMPS ARE TO BE | | ANCHORED TO MEET 140 MILES PER HOUR WINDSPER FBC-2004 | | SECTIONS1603.1.4 WIND DESIGN DATA, AND1609.1.3 | | ANCHORAGE AGAINST OVERTURNING, UPLIFT AND SLIDING. | | | | 2. PROVIDE NOTICE OF COMMENCEMENT RECORDED WITH THE | | CLERK OF THE COURT BEFORE A PERMIT CAN BE ISSUED. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|