Plan Review Notes
Plan Review Notes For Permit 06110744
Permit Number 06110744
Review Stop P
Sequence Number 2
Notes
Date Text
2007-02-03 09:33:14DENIED;
 1. SEE ELECTRICAL NOTES # 1 AND # 3.
 2. A/C DRAWING PAGE M2.1 SHOWS THE RETURN AIR IS NOT
 DUCTED, SO AREA ABOVE DROPPED CEILING IS A PLENUM.
 PLEASE REVISE NOTE # 11 ON PLUMBINGNOTES , PAGE
 P0.1, TO READ NO PVC TO BE USED.
 3. LAST REVIEW #5WAS NOT ADDRESSED. WATER HAMMER
 ARRESTORS TO BE INSTALLED PER MANUFACTURE'S
 INSTALLATION INSTRUCTIONS, AS CLOSED TO THE SOURCE,
 (FIXTURE) AS POSSIBLE. ONE WATER RISER DIAGRAM MARKED
 IN RED.