Plan Review Notes
Plan Review Notes For Permit 06110744
Permit Number 06110744
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-03 10:02:27DENIED;
 1.PLEASE SHOW HANDICAP CLEAR FLOOR SPACE ON FLOOR PLAN
 FOR BREAK SINK AND LAVATORY, AND THE TURNING RADIUS IN
 BATHROOM.
 2.SHOW A DETAIL OF BREAK SINK WITH ALL MEASUREMENT
 REQUIRED TO MEET H/C REQUIREMENTS SEE FBC-2004 CHAPTER
 11 SEC. 11-4.24.2 THRU 11-4.24.7.
 3.SHOWA DETAIL OF BATHROOM WITH ALL REQUIRED
 MEASUREMENTS W/C SEC11-4.16.2 THRU 11-4.16.7 AND
 LAVATORY 11-4.19.2 THRU 11-4.19.6.
 4.BATHROOM DOOR TO SWING OUT. CANNOT SWING INTO CLEAR
 FLOOR SPACE OF LAV.
 5. WATER HAMMER ARRESTORS ARE TO BE INSTALLED PER
 FBC-2004 PLUMBING SECTION 604.9 AND MANUFACTURER'S
 SPECIFICATIONS, AS CLOSE TO THE SOURCE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695