Plan Review Notes
Plan Review Notes For Permit 06110744
Permit Number 06110744
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-10 08:26:42** UNSAT **
  
  
 1) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE
 ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS
 INFORMATION ETC.
 PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM
 IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE
 REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER. (IF APPLICABLE).
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 2) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES
 RELEVANT TO THIS PROJECT AND DESIGN.
 2002 NFPA-72, 2002 NFPA-70, 2003 NFPA-101
 ** 2004 FBC**
  
 3) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL
 PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER
 RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON
 "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL
 LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES
 FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS
 MAX FOR TIMER TYPE)
 PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM.
 PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE
 SEE STORAGE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
 ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET
 SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT
 BE FULLY ACCOMPLISHED AT THIS TIME.
  
 4) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY
 AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE
 CONTROL DEVICES PER 700.12E. PLEASE SEE A
 CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS
 BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT
 LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER
 DEVICES.
  
 5) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 6) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE
 FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS
 AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.)
 408.4.
 ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN.
  
 7) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-12-10 07:35:20REMOVED FROM INCOMING, WILL BEROUTED BACK TO INCOMING
 ONCE REVIEW IS DONE TO WAIT FOR COMMBOB.