2006-12-13 12:24:14 | BUILDING PLAN REVIEW |
| PERMIT: 06110744 |
| ADD: 444 W RAILROAD AVSUITE# 400 |
| CONT:PBM DEVELOPMENT |
| TEL: (561)715-1800 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) ADDITIONAL INFORMATION REQUIRED. 106.1.2* |
| THIS COMMENT SHALL DEAL WITH THE EXIT ACCESS CORRIDOR. |
| THE SHELL PERMIT REMOVED THE EXIT ACCESS CORRIDORS |
| FROM |
| |
| THEIR SCOPE OF WORK. |
| EITHER ONE OF TWO THINGS WILL NEED TO HAPPEN. UNDER THE |
| SHELL PERMIT PUT A REVISION IN TFOR THE FOURTH FLOOR |
| CORRIDORS OR MAKE THE FOURTH FLOOR CORRIDORS PART OF |
| THIS PERMIT. |
| SHEET A-02 INDICATES THAT THE EXIT ACCESS CORRIDORS ARE |
| EXISTING. |
| |
| 3) SHEET A-02THE FOLLOWING DOORS ARE MISSING THE 18" |
| ON |
| THE LATCH/ PULL SIDEOF THE DOOR: 404, 408,409 & 416. |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARANCES SHALL BE |
| CLEAR & LEVEL.11-4.4.4 PROTRUDING OBJECTS. OBJECTS |
| PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES) WITH |
| THEIR |
| LEADING EDGES BETWEEN 27 INCHES AND 80 INCHES (685 MM |
| AND 2030 MM) |
| ABOVE THE FINISHED FLOOR SHALL PROTRUDE NO MORE THAN 4 |
| INCHES (102 MM) |
| INTO WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES |
| [SEE FIGURE 11-8 (A)]. |
| OBJECTS MOUNTED WITH THEIR LEADING EDGES AT OR BELOW 27 |
| INCHES (685 MM) |
| ABOVE THE FINISHED FLOOR MAY PROTRUDE ANY AMOUNT [SEE |
| FIGURE 11-8 (A) AND |
| FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON |
| POSTS OR PYLONS MAY |
| OVERHANG 12 INCHES (305 MM) MAXIMUM FROM 27 INCHES TO |
| 80 INCHES |
| (685 MM TO 2030 MM) ABOVE THE GROUND OR FINISHED FLOOR |
| [SEE FIGURE 11-8 (C) |
| AND FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT |
| REDUCE THE CLEAR WIDTH OF AN |
| ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE 11-8 |
| (E)]. |
| 1003.3.3 HORIZONTAL PROJECTIONS. |
| ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE |
| THAN 4 INCHES (102 MM) |
| WHEN THEY ARE LOCATED BETWEEN 27 AND 80 INCHES (686 AND |
| 2032 MM) ABOVE |
| THE FLOOR. HANDRAILS CAN PROJECT UP TO 4? INCHES (114 |
| MM) FROM THE WALL. |
| |
| 4) SHEET A-02 RESTROOM 407, PLEASE PROVIDE TURNING |
| RADIUS WITHIN THE RESTROOM. |
| 11-4.2.3 WHEELCHAIR TURNING SPACE. THE SPACE REQUIRED |
| FOR A WHEELCHAIR TO M |
| AKE A 180-DEGREE TURN IS A CLEAR SPACE OF 60 INCHES |
| (1525 MM) DIAMETER [SEE |
| FIGURE 11-3 (A)] OR A T-SHAPED SPACE [SEE FIGURE 11-3 |
| (B)]. |
| |
| 5) SHEET A-02 RESTROOM PLEASE INDICATE THE CLEAR FLOOR |
| SPACE REQUIRED FOR THE PLUMBING FIXTURES. 11-4.22.2 |
| DOORS. ALL DOORS TO |
| ACCESSIBLE TOLIET ROOMS SHALL COMPLY |
| WITH 11-4.13. DOORS SHALL NOT SWING INTO |
| CLEAR FLOOR SPACE REQUIRED FOR ANY |
| FIXTURE. |
| |
| 6) SHEETA-06 BREAK ROOM THE PLANS DO NOT INDICATE A |
| SINK BUT THE PLUMBING ISOMETRIC DOES. |
| PLEASE PROVIDE CABINET DETAILSCOMPLYING WITH: |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER NO HIGHER |
| THAN 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| |
| 7)SHEET A-05 INDICATES VARIOUS DETAILS WITH CROWN |
| MOULDINGS, NO MENTION OF TYPE OF MATERIAL, |
| 2604.1 GENERAL. |
| PLASTIC MATERIALS INSTALLED AS INTERIOR FINISH OR TRIM |
| SHALL COMPLY WITH CHAPTER 8 . FOAM PLASTICS SHALL ONLY |
| BE INSTALLED AS INTERIOR FINISH WHERE APPROVED IN |
| ACCORDANCE WITH THE SPECIAL PROVISIONS OF SECTION |
| 2603.8 . FOAM PLASTICS THAT ARE USED AS INTERIOR FINISH |
| SHALL ALSO MEET THE FLAME SPREAD INDEX REQUIREMENTS FOR |
| INTERIOR FINISH IN ACCORDANCE WITH CHAPTER 8 . FOAM |
| PLASTICS INSTALLED AS INTERIOR TRIM SHALL COMPLY WITH |
| SECTION 2604.2 . |
| TRIM |
| 2604.2 INTERIOR TRIM . |
| FOAM PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH |
| SECTIONS 2604.2.1 THROUGH 2604.2.4 . |
| |
| 2604.2.1 DENSITY. |
| THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20 |
| PCF (320 KG/M 3 ). |
| |
| 2604.2.2 THICKNESS. |
| THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 0.5 |
| INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES |
| (204 MM). |
| |
| 2604.2.3 AREA LIMITATION. |
| THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10 |
| PERCENT OF THE AGGREGATE WALL AND CEILING AREA OF ANY |
| ROOM OR SPACE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |