2006-12-22 14:07:10 | *** DENIED *** | | 1) PLEASE SUBMIT SITE PLAN SHOWING SPRAY BOOTH EXHAUST | | DUCT LOCATION TO PROPERTY LINES, BUILDING, AND HEIGHT | | OF EXHAUST OUTLET. SEE 2004 FBC/M 502.7.3.6. (I COULD | | NOT FIND THIS INFORMATION ON THE BUILDING PLANS | | SUBMITTED FOR PERMIT #06010452). | | | | 2) SHOW HOW EXHAUST DUCT IS TO BE SECURED TO WITHSTAND | | 140 MPH WINDS, SEE 2004 FBC 1609. | | | | 3) IF USING A GAS HEATER PLEASE PROVIDE INFORMATION | | REGARDING COMBUSTION AND MAKE-UP AIR, SEE 2004 FBC/M | | 701.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|