2007-01-10 07:03:09BUILDING PLAN REVIEW
 PERMIT: 06110667
 ADD: 422 SUNSET RD
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)718-2602
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PLEASE SUBMIT PLANS FOR THE PREMANUFACTURED SPRAY
 BOOTH, & PAINT MIXING ROOM.
 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS
 AND HORIZONTAL ASSEMBLIES OR
 BOTH WITH NOT LESS THAN A 1-HOUR FIRE-RESISTANCE
 RATING.
  
 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM
 SHALL NOT BE USED.
  
  
 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION
 OF FLAMMABLE MIST OR VAPORS IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, MECHANICAL .
 WHERE SUCH SPACES ARE NOT SEPARATELY ENCLOSED,
 NONCOMBUSTIBLE SPRAY CURTAINS SHALL
 BE PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE
 VAPORS.
  
 PLEASE PROVIDE INFORMATION HOW THE EXHAUST DUCT AND
 ROOF VENT WILL STAY ATTACHED TO THE ROOF IN A 140MPH
 EVENT.
 NO PERMIT APPLICATION HAS BEEN FILED TO HOOK UP THE
 EXHAUST DUCT FOR THE SPRAY BOOTH NOR THE GAS FIRED
 HEATER FOR SPRAY BOOTH.
  
 416.4 FIRE PROTECTION.
 AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE
 PROVIDED IN ALL SPRAY , DIP AND IMMERSING SPACES AND
 STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE
 WITH CHAPTER 9 .PLEASE PROVIDE ADITIONAL INFORMATION.
 AT THIS TIME THERE HAS BEEN NO PERMIT APPLICATION BEEN
 FILED FOR THE FIRE SUPRESSION SYSTEM THAT IS REQUIRED
 FOR THE SPRAY BOOTH. SHEET 3 OF 4 INDICATES UNIT TO BE
 DESIGNED TO:
 A) AUTOMATIC WATER SPRINKLERS
 B) DRY CHEMICAL
 C) HALON 1211/ 1301
 PLEASE HIGHLIGHT WHICH SYSTEM IS TO BE USED, AND
 PROVIDE ADDITIONAL INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  