Plan Review Notes For Permit 06110607 |
Permit Number |
06110607 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-30 17:00:03 | *****DENIED***** | | | | | | | | 1.SHEET 1 (OF THE THREE SHEET PLAN SET) UNACCEPTABLE. | | THE UPDATED PLANS ARE TO BE PRESENTED WITH NO INK, | | PENCIL, WHITE-OUTED, OR ANY OTHER HAND DRAWN MARKINGS. | | | | 2.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. | | | | 3.COORDINATE WITH THE GENERAL AND/OR FIRE CONTRACTOR | | THAT THE DOUBLE DETECTOR BE CHAINED AND LOCKED UPON THE | | COMPLETION OF THE FINAL FIRE ALARM FINAL. | | | | 4.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK | | IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY. | | | | 5.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE | | DEPARTMENT CONNECTIONS. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561805-6722 |
|