2006-11-30 17:00:03*****DENIED*****
  
  
  
 1.SHEET 1 (OF THE THREE SHEET PLAN SET) UNACCEPTABLE.
 THE UPDATED PLANS ARE TO BE PRESENTED WITH NO INK,
 PENCIL, WHITE-OUTED, OR ANY OTHER HAND DRAWN MARKINGS.
  
 2.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 3.COORDINATE WITH THE GENERAL AND/OR FIRE CONTRACTOR
 THAT THE DOUBLE DETECTOR BE CHAINED AND LOCKED UPON THE
 COMPLETION OF THE FINAL FIRE ALARM FINAL.
  
 4.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
  
 5.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  