2007-01-19 16:56:45 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SHEET A2 SPECIFIES STRUCTURE IS TYPE VI UNPROTECTED |
| CONSTRUCTION. THE 2004 FBC HAS CHANGED THIS TO |
| CONSTRUCTION TYPE V-B.PLEASE REVISE. |
| |
| 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE AWNINGS. |
| |
| 4) ADDITIONAL PERMITS WILL BE REQUIRED FOR ELECTRICAL, |
| PLUMBING, ETC. |
| |
| 5) ROOF SCUPPERS ARE REQUIRED. SPECIFY THE SIZES AND |
| LOCATIONS. THE ADDITIONAL AREA OF THE NEW ROOF AND |
| INCREASED PARAPET WALLS MUST BE CONSIDERED. 1503.4.2 |
| SCUPPER . |
| WHERE REQUIRED FOR ROOF DRAINAGE, A SCUPPER SHALL |
| BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR |
| PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY |
| THE SLOPE AND THE CONTRIBUTING AREA OF THE ROOF. THE |
| EXTERIOR FACING OR LINING OF ASCUPPER , IF |
| METAL, SHALL BE THE SAME AS FLASHING MATERIAL REQUIRED |
| BY SECTIONS 1503 THROUGH 1510 FOR THE PARTICULAR TYPE |
| OF COVERING SPECIFIED FOR THE BUILDING. FOR OTHER TYPE |
| MATERIALS, FOLLOW MANUFACTURER?S SPECIFICATIONS. |
| 1503.4.3 |
| WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS |
| NOT PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN |
| WALLS OR PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR |
| MORE THAN 4 INCHES (102 MM) ABOVE THE FINISHED ROOF |
| COVERING AND SHALL BELOCATED AS CLOSE AS PRACTICAL |
| TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND |
| PARAPET SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| |
| 6) 1503.6 PROTECTION AGAINST DECAY AND TERMITES. |
| CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| A ROOF ABOVE ANOTHER ROOF. |
| |
| 7)THE SECTION MARKER FOR 3 / A3.1 ON SHEET A2 IS |
| INCORRECTLY INDICATED THROUGH THE THE WINDOW INSTEAD OF |
| THE DOOR. |
| |
| 8) PLEASE INDICATE THE PROPERTY LINES IN RELATION TO |
| THE STRUCTURE. 3202.3 ENCROACHMENTS 8 FEET OR MORE |
| ABOVE GRADE. |
| ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE |
| SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4 . |
| |
| 3202.2.2 ARCHITECTURAL FEATURES. |
| COLUMNS OR PILASTERS, INCLUDING BASES AND MOLDINGS |
| SHALL NOT PROJECT MORE THAN 12 INCHES (305 MM). BELT |
| COURSES, LINTELS, SILLS, ARCHITRAVES, PEDIMENTS AND |
| SIMILAR ARCHITECTURAL FEATURES SHALL NOT PROJECT MORE |
| THAN 4 INCHES (102 MM). |
| |
| 9)ON SHEET S3 THE ROOF SHEATHING FASTENER SPACING IS |
| INCORRECT. FBC TABLE 2304.9.1 REQUIRES 6" OC AT ZONES 1 |
| & 2AND 4" OC IN ZONE 3. |
| |
| 10)SUBMIT PRODUCT APPROVALS FOR THE FOOF COVERING AT |
| THE NEW ROOF AREA. |
| |
| 11) THE WRONG FLORIDA PRODUCT APPROVAL COVER SHEET & |
| FL# FOR THE 3000/L-3000 STOREFRONTS WAS SUBMITTED. THE |
| CORRECT ONE IS FL6297. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |