Plan Review Notes
Plan Review Notes For Permit 06110605
Permit Number 06110605
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-19 16:56:45DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SHEET A2 SPECIFIES STRUCTURE IS TYPE VI UNPROTECTED
 CONSTRUCTION. THE 2004 FBC HAS CHANGED THIS TO
 CONSTRUCTION TYPE V-B.PLEASE REVISE.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE AWNINGS.
  
 4) ADDITIONAL PERMITS WILL BE REQUIRED FOR ELECTRICAL,
 PLUMBING, ETC.
  
 5) ROOF SCUPPERS ARE REQUIRED. SPECIFY THE SIZES AND
 LOCATIONS. THE ADDITIONAL AREA OF THE NEW ROOF AND
 INCREASED PARAPET WALLS MUST BE CONSIDERED. 1503.4.2
 SCUPPER .
 WHERE REQUIRED FOR ROOF DRAINAGE, A SCUPPER SHALL
 BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY
 THE SLOPE AND THE CONTRIBUTING AREA OF THE ROOF. THE
 EXTERIOR FACING OR LINING OF ASCUPPER , IF
 METAL, SHALL BE THE SAME AS FLASHING MATERIAL REQUIRED
 BY SECTIONS 1503 THROUGH 1510 FOR THE PARTICULAR TYPE
 OF COVERING SPECIFIED FOR THE BUILDING. FOR OTHER TYPE
 MATERIALS, FOLLOW MANUFACTURER?S SPECIFICATIONS.
 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS
 NOT PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN
 WALLS OR PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR
 MORE THAN 4 INCHES (102 MM) ABOVE THE FINISHED ROOF
 COVERING AND SHALL BELOCATED AS CLOSE AS PRACTICAL
 TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 6) 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 7)THE SECTION MARKER FOR 3 / A3.1 ON SHEET A2 IS
 INCORRECTLY INDICATED THROUGH THE THE WINDOW INSTEAD OF
 THE DOOR.
  
 8) PLEASE INDICATE THE PROPERTY LINES IN RELATION TO
 THE STRUCTURE. 3202.3 ENCROACHMENTS 8 FEET OR MORE
 ABOVE GRADE.
 ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE
 SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4 .
  
 3202.2.2 ARCHITECTURAL FEATURES.
 COLUMNS OR PILASTERS, INCLUDING BASES AND MOLDINGS
 SHALL NOT PROJECT MORE THAN 12 INCHES (305 MM). BELT
 COURSES, LINTELS, SILLS, ARCHITRAVES, PEDIMENTS AND
 SIMILAR ARCHITECTURAL FEATURES SHALL NOT PROJECT MORE
 THAN 4 INCHES (102 MM).
  
 9)ON SHEET S3 THE ROOF SHEATHING FASTENER SPACING IS
 INCORRECT. FBC TABLE 2304.9.1 REQUIRES 6" OC AT ZONES 1
 & 2AND 4" OC IN ZONE 3.
  
 10)SUBMIT PRODUCT APPROVALS FOR THE FOOF COVERING AT
 THE NEW ROOF AREA.
  
 11) THE WRONG FLORIDA PRODUCT APPROVAL COVER SHEET &
 FL# FOR THE 3000/L-3000 STOREFRONTS WAS SUBMITTED. THE
 CORRECT ONE IS FL6297.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  