 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE FEEDER CONDUCTORS DO NOT HAVE THE AMPACITY FOR
 THE 100 AMP OCP. 310.16. INDICATE THE VOLTAGE OF THE
 SERVICE.
  
 2} INDICATE THE OCP FOR THE #6 CONDUCTORS FEEDING THE
 POLES.
  
 3} PLEASE SUBMIT SPECIFICATIONS FOR THE POLES INDICATED
 ON THE PLAN, INCLUDE AMPERAGE AND VOLTAGE RATINGS FOR
 THE LUMINAIRES.
  
 4} PROVIDE A RISER DIAGRAM OF THE PROPOSED SERVICE.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2., BOTH
 SETS.
  