2007-01-04 15:14:13 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE FEEDER CONDUCTORS DO NOT HAVE THE AMPACITY FOR | | THE 100 AMP OCP. 310.16. INDICATE THE VOLTAGE OF THE | | SERVICE. | | | | 2} INDICATE THE OCP FOR THE #6 CONDUCTORS FEEDING THE | | POLES. | | | | 3} PLEASE SUBMIT SPECIFICATIONS FOR THE POLES INDICATED | | ON THE PLAN, INCLUDE AMPERAGE AND VOLTAGE RATINGS FOR | | THE LUMINAIRES. | | | | 4} PROVIDE A RISER DIAGRAM OF THE PROPOSED SERVICE. | | | | 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2., BOTH | | SETS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|