2008-03-14 12:30:01 | BUILDING REVIEW COMMENTS | | | | | | ALL NEW MECHANICAL EQUIPMENT SHALL BE INSTALLED AT THE | | MINIMUM ELEVATION OF 7.5' IN FLOOD ZONE A-5. THE | | ELEVATION CERTIFICATE PROVIDED LISTS THE EQUIPMENT AT | | 6.1'. | | | | PLEASE PROVIDE A TERMITE TREATMENT CERTIFICATE FROM | | HULETT ENVIRONMENTAL SERVICES STATING THAT ALL | | AREASUNDER THE NOW EXISTING STRUCTURE HAVE BEEN TREATED | | FOR TERMITES. THE INFORMATION PROVIDED FROM HULETT | | SERVICES IS NOT CLEAR WHETHER IT COVERS THE ENTIRE | | FOOTPRINT OF THE BUILDING. | | | | ADDITIONAL PERMITS ARE REQUIRED FOR MECHANICAL, | | PLUMBING, ELECTRICAL, ETC,,,,, | | | | SUBMIT THE INDEPENDENT EQUIPMENT TESTING COMPANY'S | | CALIBRATION CERTIFICATES FOR THE EQUIPMENT (MANIFOLD, | | LOAD CELLS, ETC.) USED TO LIFT THE HOUSE, SO THAT THE | | ACCURACY OF THE STATED HOUSE WEIGHT CAN BE VERIFIED. | | | | SUBMIT ENGINEER'S CALCULATIONS TO SHOW THAT, SINCE | | THERE ARE NO REBAR TIES BETWEEN THE FOUNDATION CONCRETE | | AND THE STEM WALL, THE WEIGHT OF THE HOUSE IS | | SUFFICIENT TO RESIST SHEAR (I.E. SLIDING OFF THE | | FOUNDATION) AND UPLIFT (RESULTING FROM OVERTURNING | | ACTION) DUE TO THE WIND PRESSURES DERIVED FROM 140 MPH | | WIND SPEED. | | | | | | | | | | | | | | | | LUIS MARTINEZ | | 561-805-6710 |
|