Plan Review Notes
Plan Review Notes For Permit 06110563
Permit Number 06110563
Review Stop M
Sequence Number 2
Notes
Date Text
2007-03-15 15:20:10*** DENIED ***
 1) AS NOTED IN LAST REVIEW 11-21-06 NOTE #2. SEE
 COOLING LOAD CALCULATIONS SHOW THAT ALL FIVE BAYS
 TOGETHER WILL NEED OVER 460 TONS OF A/C, PLEASE SUBMIT
 CORRECTED COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-407.1.ABC.1.
  
 2) THE ENGINEER EDWARD J. KRANZ WILL NEED TO SEAL THE
 MECHANICAL PLANS AS HIS INFORMATION IS IN THE TITLE
 BLOCK, SEE FAC 61G15-23.002. (SEE PLANS, PAGES M-1 AND
 M-2).
  
 3) SEE PLANS, PAGE M-1 "O/A INTAKE" IF THIS IS TYPICAL
 OF 5 PLEASE STATE SO ON PLANS IF NOT GIVE INFORMATION
 AT EACH INTAKE.
  
 4) SEE PLANS, PAGE M-1 " 6 INCH DUCT TO EXHAUST WALL
 LOUVER" IF TYPICAL OF 5 STATE SO ON PLANS IF NOT GIVE
 INFORMATION AT EACH EXHAUST.
  
 5) SEE PLANS, PAGE 4 ELECTRICAL PLANS SHOW 7 A/C
 CONDENSER UNITS, MECHANICAL PLANS ONLY SHOW 5, PLEASE
 CORRECT ELECT. PLANS.
  
 6) SEE PLANS, PAGE M-2A/C SCHEDULE SHOWS THE WRONG
 EQUIPMENT MANUFACTURE, CAPACITY (TOTAL) BTU'S, SENSIBLE
 BTU'S, AND A INCORRECT MODEL NUMBER FOR AHU #1. PLEASE
 REVIEW SUBMITTED MANUFACTURER'S SPECIFICATION'S FOR THE
 GOODMAN A/C AND CORRECT.
  
 7) SEE ELECTRICAL REVIEW NOTE #2 AND 3. AS A RESULT OF
 DOCUMENTS BEING RETAINED PLEASE BE CERTAIN TWO COPY'S
 OF ALL INFORMATION IS BEING SUBMITTED.
  
 8)SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.