2007-03-20 13:45:36 | BUILDING PLAN REVIEW |
| PERMIT: 06110563 |
| ADD: 2814 S.DIXIE HWY #101 |
| CONT: KARNS CONST. CORP. |
| TEL: (561)805-7528 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 2ND |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FBC. 106.3.5THE EXAMINATION OF THE DOCUMENTS BY |
| THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING |
| MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE |
| PLAN; FOUNDATION PLAN; FLOOR/LAYOUT;AND ALL EXTERIOR |
| ELEVATIONS WITH THE ACCESSIBLE ROUTE TO EACH UNIT IN |
| COMPLIANCE WITH FBC. 11-4.3. |
| |
| 3)106.1.1W.P.B. ADMINISTRATIVE CODE CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE. |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| CODES. |
| SUCH INFORMATION SHALL BE SPECIFIC |
| AND THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE |
| TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". |
| |
| 4)IF THE NEW 4" CONCRETE SLAB IS CONSTRUCTED AT EACH |
| DOOR HOW DOES EACH ENTRANCE COMPLY WITH THE |
| ACCESSIBILITY CODE? SHOW COMPLIANCE. SEE 2004 FBC. FIG |
| 11 AND 12 OF CH. 11.SHEET 1 SHOWS THE ACCESSIBLE |
| ROUTE TO SUITE 'A' ONLY WHAT ABOUT THE OTHER SUITES? |
| ALSO FBC. 11-4.8.1 ANY PARTOF AN ACCESSIBLE ROUTE WITH |
| A SLOPE GREATER THAN 1:20 SHALL BE CONSIDERED A RAME |
| AND SHALL COMPLY WITH SECTION 11-4.8. |
| |
| 5)WHEN RESUBMITING, HAVE THE FRONT COUNTER STAFF |
| ADJUST THE VALUE OF THE PROJECT AND PAY THE ADDITIOINAL |
| FEES ACCORDINGLY. FOR MORE INFORMATION SEE WPB. |
| AMENDMENTS 108.3. |
| |
| 6)SEE INFORMATION ABOUT THE CONSTRUCTION OF THE |
| DUMPSTER ENCLOSURE IN THE PACKAGE AND FOLLOW THOSE |
| GUIDELINES. |
| |
| 7)FBC. 1210.2 WALLS WITHIN 2 FEET OF WATER CLOSETS |
| SHALL HAVE A SMOOTH, HARD, AND NONABLORBENT SURFACE, TO |
| A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR |
| STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. |
| |
| 8)ALL THE PRODUCT APPROVALS SUBMITTED SHALL BE |
| APPROVED IN WRITING "(NO PHOTO-COPIES ALLOWED)" BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL.THE ONES |
| SUBMITTED ARE PHOTOCOPIES. WPB.AMENDMENTS 106.3.3. |
| |
| 9)ALL PAGES SUBMITTED SHALL BE SIGNED, DATED AND SEAL |
| BY THE ARCHITECT OR ENGINEER IN RESPONSIBLE CHARGE. SEE |
| F.A.C. 61G15-23.002 AND 61G1-16.004 / 471.025. FOR MORE |
| INFORMATION. THE MECHINICAL SHEETS (M-1) HAS A |
| CORPORATE SEAL. THIS SEAL HAS NO BEARING ON THE |
| DRAWINGS. SHEET (M-2) IS NOT SEAL. NOTE ALL SIGNATURES |
| SHALL BE ORIGINAL. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |