Plan Review Notes
Plan Review Notes For Permit 06110563
Permit Number 06110563
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-26 10:26:57DENIED;
 1.SHOW SIZE AND CALCULATIONS OF ROOF GUTTERS AND DOWN
 SPOUTS TO COMPLY WITH FBC-2004 PLUMBING CHAPTER 11
 TABLES 1106.2 AND 1106.6.
 2. SANITARY RISER DIAGRAM IS MISSING A DRINKING
 FOUNTAIN.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695