2006-11-21 15:55:42*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.6 .
  
 2) SEE COOLING LOAD CALCULATIONS PAGE 1, LOAD CAL'S
 SHOW THAT ALL FIVE BAYS TOGETHER WILL NEED OVER 460
 TONS OF A/C, PLEASE RE-DO LOAD CAL'S.
  
 3) CONDENSER UNITS APPEAR TO BE LOCATED IN THE BACK
 OFFICES, PLEASE CORRECT..
  
 4) PLEAS SHOW ON THE PLANS EQUIPMENT LISTING, THE
 SENSIBLE AND TOTAL BTU'S.
  
 5) PLEASE SHOW THE LOCATION OF ALL GRILLS.
  
 6) SEE UNIT B, PLEASE LABEL GRILLS IN BACK OFFICE.
  
 7) PLEASE PROVIDE DETAIL ON BATHROOM EXHAUST DUCTS, ARE
 THEY INDEPENDENTLY DUCTED TO THE OUTDOORS?
  
 8) PLEASE SHOW THE SIZE OF ALL SUPPLY AND RETURN AIR
 DUCTS (SEE HIGH LIGHTS ON PLANS).
  
 9) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.