2006-11-21 15:55:42 | *** DENIED *** | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | 13-101.1.1.6 . | | | | 2) SEE COOLING LOAD CALCULATIONS PAGE 1, LOAD CAL'S | | SHOW THAT ALL FIVE BAYS TOGETHER WILL NEED OVER 460 | | TONS OF A/C, PLEASE RE-DO LOAD CAL'S. | | | | 3) CONDENSER UNITS APPEAR TO BE LOCATED IN THE BACK | | OFFICES, PLEASE CORRECT.. | | | | 4) PLEAS SHOW ON THE PLANS EQUIPMENT LISTING, THE | | SENSIBLE AND TOTAL BTU'S. | | | | 5) PLEASE SHOW THE LOCATION OF ALL GRILLS. | | | | 6) SEE UNIT B, PLEASE LABEL GRILLS IN BACK OFFICE. | | | | 7) PLEASE PROVIDE DETAIL ON BATHROOM EXHAUST DUCTS, ARE | | THEY INDEPENDENTLY DUCTED TO THE OUTDOORS? | | | | 8) PLEASE SHOW THE SIZE OF ALL SUPPLY AND RETURN AIR | | DUCTS (SEE HIGH LIGHTS ON PLANS). | | | | 9) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|