Plan Review Notes
Plan Review Notes For Permit 06110563
Permit Number 06110563
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-07 08:49:05*** UNSAT ***
  
 1) NOTE:PLEASE SEE LOADS FOR SHOW WINDOWS NEED TO BE
 CLARIFIED PER 220.12A. PLEASE SEE AS THE VA IS NOT
 SHOWN AND NO LOAD SUMMARY IS SHOWN, THE VA PER FOOT CAN
 NOT BE VERIFIED.
 210.62
  
 2) NOTE: PLEASE VERIFY THE LOAD SHOWN FOR THE SIGN
 CIRCUIT(S). PLEASE SEE 600.5, WHICH REFERENCES TO
 220.3B6 FOR THE MINIMUM VA TO USE TO FIGURE FOR SIGN
 CIRCUITS. PLEASE SEE THE LOAD OF 5A?S FOR EACH DOES NOT
 CORRELATE TO THE MINIMUM VA REQUIRED.
 PLEASE SEE NO LOAD SUMMARY IS SHOWN TO VERIFY THIS.
  
 3) NOTE: PLEASE CORRELATE LOADS ON PANEL FOR KNOWN
 RECEPTS ON A CIRCUIT. 220.13
  
 4) NOTE: PLEASE SEE A NOTE ON "E" UNIT INDICATES
 RECEPTACLE ABOVE CEILING AS TYPICAL FOR EACH SIGN
 CIRCUIT. PLEASE SEE 600.5, AS IT ONLY REQUIRES A
 CIRCUIT. PLEASE SEE 400.8(2) WHICH DO NOT PERMIT
 RECEPTACLES ABOVE CEILINGS AS THIS WOULD THEN CREATE
 THE ISSUE OF CORDS BEING RUN THROUGH CEILINGS WHICH IS
 NOT PERMITTED.
 PLEASE REVISE.
  
 5) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM
 AS SHOWN. RISER SHOWS THE MAIN GROUNDING ELECTRODE
 BEING "TAPPED" AND SHOWN TO EACH MAIN DISCONNECT??
 PLEASE SEE 250.24B, 250.6. PLEASE KNOW WHEN INSTALLING
 THE GUTTER, THE NEUTRAL CONDUCTOR WOULD BE "BONDED" TO
 THE GUTTER WHICH MAY CONTAIN THE SOLE CONNECTION OF THE
 GEC. PLEASE SEE ONLY ONE SET OF PHASE AND NEUTRAL
 CONDUCTORS WOULD THEN BE ROUTED TO EACH METER AND MAIN.
 EACH NEUTRAL WOULD BE BONDED TO THE ENCLOSURE AT THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE AS SHOWN THIS SEEM TO BE AN INTERESTING
 SCENARIO AT THE CONNECTION POINT SHOWN AT THE GROUND
 LEVEL LOCATION.
 ** PLEASE SEE THIS BEING AN EXISTING BUILDING AND THE
 CONCRETE ENCASED ELECTRODE ON AN EXISTING BUILDING IS
 NOT REQUIRED TO BE ATTACHED. PLEASE KNOW IF SHOWN ON
 GROUNDING ELECTRODE DETAIL BEING REQUIRED THEN THIS
 WILL BE REQUIRED IN THE FIELD. PLEASE VERIFY THIS BEING
 REQUIRED AND POSSIBLY AFFECTING THE STRUCTURAL
 INTEGRITY OF THE EXISTING FOOTER.
  
 6) NOTE: PLEASE LIST THE FOLLOWING RELEVANT CODES ON
 THE PLANS. 2002 NFPA-70, 2003 NFPA-101
  
 7) NOTE: PLEASE CORRELATE LOADS, OVER CURRENT
 PROTECTION, CONDUCTORS ETC FOR THE A/C SYSTEMS. PLEASE
 SEE ELECTRICAL PLANS SEEM TO INDICATE A POSSIBLE 5KW
 LOAD, HOWEVER AS KW RATINGS/ KVA LOADS ARE NOT SHOWN,
 THESE ARE UNCLEAR AT THIS TIME. PLEASE SEE MECHANICAL
 PLANS CALL FOR 8KW AND 10KW UNITS.
 PLEASE SEE 424.3B, 310.16, 240.4 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved