Date |
Text |
2007-03-10 18:18:40 | ** UNSAT 2ND REVIEW ** |
| |
| |
| 1) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING PLANS |
| WITH THE ENERGY CALCULATIONS SUBMITTED. PLEASE SEE THE |
| NUMBER OF FIXTURES; THE WATTAGE PER FIXTURE AND THE |
| TOTAL DO NOT CORRELATE WITH THAT OF THE FIXTURES AND |
| LIGHTING ON PLANS. |
| PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE AN |
| EXTERIOR LIGHTING, YET THE PLANS INDICATE EXTERIOR |
| LIGHTING. |
| 13-415.1.AB.1.1 |
| 13-415.2 |
| |
| 2) NOTE: PLEASE SEE FBC 103.1, 103.1.1.1 AS THE ENERGY |
| CALCULATIONS MUST BE SIGNED, DATED AND SEALED BY THE |
| DESIGN PROFESSIONAL EVEN WHEN/IF FALLING UNDER THE |
| EXCEPTIONS THAT A MECHANICAL CONTRACTOR PERFORMS THE |
| SCOPE OF WORK. |
| PLEASE KNOW THE SCOPE DOES NOT APPEAR TO FALL UNDER THE |
| EXCEPTIONS UNDER FS 471.003. |
| ** PLEASE ALSO SEE THE MECHANICAL PLANS WHICH CONTAIN |
| TITLE BLOCKS FROM AN ENGINEER AND ENGINEERING FIRM, YET |
| THERE IS A SIGNATURE AND SEAL ON THESE SHEETS FROM A |
| MECHANICAL CONTRACTOR. THIS IS NOT PERMITTED UNDER |
| FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE |
| CODE 61G15-23.002 |
| PLEASE ALSO SEE THE 2ND MECHANICAL SHEET IN EACH SET |
| DOES NOT CONTAIN ANY SIGNATURE, DATE OR SEAL FROM |
| ANYONE. |
| |
| 3) NOTE: PLEASE KNOW DUE TO THE COMMENTS ONE SET OF |
| PLANS AND ENERGY CALCULATIONS WILL BE RETAINED BY THIS |
| OFFICE. |
| **PLEASE BE SURE RE-PRINT THE 2ND SET OF ELECTRICAL. AS |
| PLUMBING IS ON THE SAME SHEET WITH ELECTRICAL, PLUMBING |
| WILL NEED TO RE-STAMP SHEETS IN SETS WHEN PLANS ARE |
| CORRECTED AND RESUBMITTED. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |