Date Text
2007-03-10 18:18:40** UNSAT 2ND REVIEW **
  
  
 1) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING PLANS
 WITH THE ENERGY CALCULATIONS SUBMITTED. PLEASE SEE THE
 NUMBER OF FIXTURES; THE WATTAGE PER FIXTURE AND THE
 TOTAL DO NOT CORRELATE WITH THAT OF THE FIXTURES AND
 LIGHTING ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE AN
 EXTERIOR LIGHTING, YET THE PLANS INDICATE EXTERIOR
 LIGHTING.
 13-415.1.AB.1.1
 13-415.2
  
 2) NOTE: PLEASE SEE FBC 103.1, 103.1.1.1 AS THE ENERGY
 CALCULATIONS MUST BE SIGNED, DATED AND SEALED BY THE
 DESIGN PROFESSIONAL EVEN WHEN/IF FALLING UNDER THE
 EXCEPTIONS THAT A MECHANICAL CONTRACTOR PERFORMS THE
 SCOPE OF WORK.
 PLEASE KNOW THE SCOPE DOES NOT APPEAR TO FALL UNDER THE
 EXCEPTIONS UNDER FS 471.003.
 ** PLEASE ALSO SEE THE MECHANICAL PLANS WHICH CONTAIN
 TITLE BLOCKS FROM AN ENGINEER AND ENGINEERING FIRM, YET
 THERE IS A SIGNATURE AND SEAL ON THESE SHEETS FROM A
 MECHANICAL CONTRACTOR. THIS IS NOT PERMITTED UNDER
 FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002
 PLEASE ALSO SEE THE 2ND MECHANICAL SHEET IN EACH SET
 DOES NOT CONTAIN ANY SIGNATURE, DATE OR SEAL FROM
 ANYONE.
  
 3) NOTE: PLEASE KNOW DUE TO THE COMMENTS ONE SET OF
 PLANS AND ENERGY CALCULATIONS WILL BE RETAINED BY THIS
 OFFICE.
 **PLEASE BE SURE RE-PRINT THE 2ND SET OF ELECTRICAL. AS
 PLUMBING IS ON THE SAME SHEET WITH ELECTRICAL, PLUMBING
 WILL NEED TO RE-STAMP SHEETS IN SETS WHEN PLANS ARE
 CORRECTED AND RESUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  