2006-12-12 16:19:10 | *****DENIED***** |
| |
| |
| |
| 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| |
| 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS |
| SHALL COMPLY WITH NFPA 241. |
| |
| 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE |
| REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE |
| FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| |
| 5.GASOLINE POWERED EQUIPMENT FOR DEMOLITION |
| ACTIVITIES SHALL NOT BE USED TO PREVENTTHE |
| POSSIBILITY OF CARBON DIOXIDE POISONING. |
| |
| 6.SHOW/DISPLAY THE ADDRESS OF THE STRUCTURE ON THE |
| EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY. AS |
| PER WEST PALM BEACH CODE, THE NUMERICAL ADDRESS SHALL |
| BE NO LESS THAN 6' IN HEIGHT AND 1" IN WIDTH. |
| ADDITIONALLY, DISPLAY THE UNIT NUMBER (3" IN HEIGHT AND |
| 1" IN WIDTH) FOR THE FRONT ENTRANCE TO DISTINGUISH ONE |
| UNIT FROM THE OTHER. FRONT UNIT NUMBERS SHALL NOT BE ON |
| THE DOORS OR WINDOWS, HOWEVER REAR UNIT NUMBER CAN BE |
| INSTALLED ON THE DOOR.HURRICANE SHUTTERS SHALL NOT |
| BLOCK VISIBILITY OF BUILDING AND/OR UNIT ADDRESS. |
| |
| 7.INTERIOR FINISH CLASSIFICATION IN AN UNSPRINKLERED |
| BUILDING SHALL BE "A" OR "B". |
| |
| 8.FIRE EXTINGUISHERS TO BE 2A:10BC RATED. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| |