Plan Review Notes
Plan Review Notes For Permit 06110559
Permit Number 06110559
Review Stop B
Sequence Number 1
Notes
Date Text
2006-12-21 11:40:56BUILDING PLAN REVIEW
 PERMIT: 06110559
 ADD: 2814 S. DIXIE HWY.
 CONT: KARNS CONSTRUCTION CORP.
 TEL: (561)805-7528
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST.
 ACTION: DENIED
  
 NOTE: ANY OTHER OCCUPANCY OTHER THAN WHAT IS STATED BY
 THE DESIGNER OF RECORD SHALL REQUIRE A SEPERATE
 PERMIT.
  
 1) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA. RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT PRODUCT APPROVALS FOR
 THE IMPACT WINDOWS/DOORS/ROOF AND STOREFRONT.
  
 2)W.P.B. AMENDMENTS 108.3*IF IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING,ALTERATION APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL,ELECTRIC,PLUMBING,MECHANICAL,INTERIOR
 FINISH,ARCHITECTURAL AND DESIGN FEES,MARKETING COSTS,
 AND OVERHEAD AND PROFIT. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES.
  
 3)SHEET #1. IN REFERENCE TO THE DUMPSTER PAD, SEE
 REQUIREMENTS DETAILS IN PACKAGE AND COMPLY
 ACCORDINGLY.
  
 4) FBC 11-4.3 SHOW THE ACCESSIBLE ROUTE TO THE BUILDING
 COMPLYING WITH THIS SECTION.
  
 5)SHEET #2. THE CODE SECTION ON THE DRAWINGS IN
 REFERENCE TO ROOF DOWNSPOUTS IS FROM THE 2001 FBC. SEE
 FBC 2004 FOR CORRECT REFERENCE.
  
 6)FBC 1503.4 UNLESS ROOF ARE SLOPED TO DRAIN OVER
 ROOF EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE
 SYSTEMS SHALL COMPLY WITH THE FBC PLUMBING CH. 11.
  
 7)1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  