Date |
Text |
2007-02-13 16:33:24 | REVISION DENIED |
| REFERENCE: FBC-2004 FUEL GAS; FLORIDA ADMINISTRATIVE |
| CODE; CITY OF WEST PALM BEACH GAS PERMIT (REVISION) |
| REQUIREMENTS; |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PLEASE NOTE THAT THE ORIGINAL CONSTRUCTION |
| DOCUMENTS ARE SIGNED, DATED AND SEALED BY AN ENGINEER. |
| PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002, ANY |
| REVISIONS TO THE CONSTRUCTION DOCUMENTS SHALL BE SIGNED |
| SEALED AND DATED BY THE ENGINEER OF RECORD EUGENE |
| PILHUJ, LICENSE NUMBER, P.E. FL. REG. 49832. PLEASE |
| CORRECT AND RESUBMIT. |
| |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED ON |
| THE REVISION, PLEASE CORRECT AND RESUBMIT. |
| |
| 3. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: NOT ALL PIPING MATERIALS OR SIZES ARE INDICATED |
| ON THE RESUBMITTAL AND PLEASE NOTE THAT THE REVISED GAS |
| DRAWING IS SIZED WRONG . PLEASE REFERENCE THE ATTACHED |
| FBC-2004 FUEL GAS SIZING TABLES FOR THE REVISION |
| RESUBMITTAL. |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: THE ADDED LONGEST LENGTH OF THE INDICATED PIPE |
| COMES TO 60'-11", BUT NOT ALL CORRESPONDING LENGTHS ARE |
| INDICATED ON ALL CUT SECTIONS OF PIPEON THE REVISION. |
| PLEASE CORRECT AND INDICATE THE LONGEST LENGTH ON THE |
| RESUBMITTED REVISION. |
| |
| 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| ON THE RESUBMITTED REVISION |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| NOTE: THE DELIVERY PRESSURE IS NOT INDICATED ON THE |
| REVISION, PLEASE CORRECT THIS ON THE RESUBMITTED |
| REVISION. |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |