Plan Review Notes
Plan Review Notes For Permit 06110515
Permit Number 06110515
Review Stop G
Sequence Number 1
Notes
Date Text
2006-12-01 13:50:08DENIED
 REFERENCE: FBC-2004 FUEL GAS AND THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS
  
 THE FOLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CITY AND CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED ISOMETRIC DRAWING DOES NOT INDICATE
 ALL CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE:THE ONLY MATERIAL INDICATED AS BEING USED IS PE.
 PER FBC-2004 FUEL GAS , SECTION 403.6 PLASTIC PIPE,
 TUBING AND FITTINGS SHALL BE USED OUTSIDE, UNDERGROUND,
 ONLY. PLEASE INDICATE ALL PIPING MATERIALS BEING USED
 (ABOVE AND UNDERGROUND) ON THE RESUBMITTED ISOMETRIC.
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 NOTE: PLEASE SUBMIT CALCULATIONS OF WATER HEATER
 LOCATION.
  
 4. ON THE MASTER PERMIT #05120933 THERE ALREADY A SHEET
 P-3. PLEASE CHANGE THE RESUBMITTEDSHEET TO P-4 TO
 ADVOID CONFUSION.
  
 5. THE LONGEST LENGTH INDICATED ON THE DRAWINGS IS
 WRONG ON THE FLOOR PLAN DRAWING THE THE LONGEST LENGTH
 CALCULATES55' AND ON THE ISOMETRIC THE LONGEST LENGTH
 CALCULATES 63' WITH THE MEASUREMENTS GIVEN BUT IS
 LISTED AS 48'. ALL THREE OF THESE CALCULATIONS ARE
 WRONG BECAUSE NOT ALL OF THE CORRESPONDING LENGTHS ARE
 INDICATED ON THE ISOMETRIC GAS RISER DIAGRAM. PLEASE
 CORRELATE THE LONGEST LENGTH ON THE RESUBMITTAL.
  
 6. PLEASE CORRELATE THE SLEEVE INDICATED ON THE FLOOR
 PLAN WITH THE ISOMETRIC GAS RISER DIAGRAM.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved