Date |
Text |
2006-12-01 13:50:08 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS AND THE CITY OF WEST PALM |
| BEACH GAS PERMIT APPLICATION REQUIREMENTS |
| |
| THE FOLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CITY AND CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE SUBMITTED ISOMETRIC DRAWING DOES NOT INDICATE |
| ALL CORRESPONDING LENGTHS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE:THE ONLY MATERIAL INDICATED AS BEING USED IS PE. |
| PER FBC-2004 FUEL GAS , SECTION 403.6 PLASTIC PIPE, |
| TUBING AND FITTINGS SHALL BE USED OUTSIDE, UNDERGROUND, |
| ONLY. PLEASE INDICATE ALL PIPING MATERIALS BEING USED |
| (ABOVE AND UNDERGROUND) ON THE RESUBMITTED ISOMETRIC. |
| |
| 3. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. |
| NOTE: PLEASE SUBMIT CALCULATIONS OF WATER HEATER |
| LOCATION. |
| |
| 4. ON THE MASTER PERMIT #05120933 THERE ALREADY A SHEET |
| P-3. PLEASE CHANGE THE RESUBMITTEDSHEET TO P-4 TO |
| ADVOID CONFUSION. |
| |
| 5. THE LONGEST LENGTH INDICATED ON THE DRAWINGS IS |
| WRONG ON THE FLOOR PLAN DRAWING THE THE LONGEST LENGTH |
| CALCULATES55' AND ON THE ISOMETRIC THE LONGEST LENGTH |
| CALCULATES 63' WITH THE MEASUREMENTS GIVEN BUT IS |
| LISTED AS 48'. ALL THREE OF THESE CALCULATIONS ARE |
| WRONG BECAUSE NOT ALL OF THE CORRESPONDING LENGTHS ARE |
| INDICATED ON THE ISOMETRIC GAS RISER DIAGRAM. PLEASE |
| CORRELATE THE LONGEST LENGTH ON THE RESUBMITTAL. |
| |
| 6. PLEASE CORRELATE THE SLEEVE INDICATED ON THE FLOOR |
| PLAN WITH THE ISOMETRIC GAS RISER DIAGRAM. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |