2007-08-06 11:42:40 | THIRD REVIEW | | 2004 FBC | | RENOVATE AND INCREASE FIRST FLOOR GARAGE AREA AND ADD | | SECOND FLOOR LIVING SPACE TO EXISTING DETACHED GARAGE | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) SHOP DRAWINGS FOR THE SPIRAL STAIR WILL BE REQUIRED | | TO BE SUBMITTED FOR PLAN REVIEW PRIOR TO INSTALLATION. | | | | 3) ROOF SECTIONS 3, 10 AND 11 ON S2 INCORRECTLY SPECIFY | | THE RAFTERS AS FLOOR JOISTS. PLEASE CORRECT. SEE | | COMMENT #14 FROM LAST REVIEW. | | | | 4) THE PRODUCT APPROVALS FOR THE SIMPSON CONNECTORS | | SUBMITTED ARE NOT APPLICABLE. THERE ARE NO SIMPSON | | CONNECTORS SPECIFIED ON THE PLANS. SEE COMMENT # 17 | | FROM LAST REVIEW. PLEASE REMOVE THESE FROM THE | | SUBMITTALS. | | | | 5) THE RAS 117 CALCULATIONS FOR THE SEALOFLEX | | WATERPROOFING SYSTEM IS INCORRECT. THE RESULTS OF THE | | CALCULATIONS HAVE THE FASTENERS ARE SPACED FARTHER | | APART THAN SPECIFIED IN THE NOA FOR THE DESIGN | | PRESSURE. THE SPACING SHOULD BE CLOSER FOR ENHANCED | | FASTENING. PLEASE CORRECT. | | | | 6) SUBMIT THE OLD PLAN SHEETS WITH THE COUNTY IMPACT | | FEE STAMP OR HAVE THE NEW ONES STAMPED BY THE COUNTY. | | | | 7) HAVE THE NEW PLANS REVIEWED AND APPROVED BY THE CITY | | OF WPB HISTORIC PLANNING DEPARTMENT. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | |
|