2007-05-30 14:17:34 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SHOW COMPLIANCE WITH 401.3 DRAINAGE. THE DRAINAGE |
| PLAN ON SP-1 DOES NOT INDICATE THE DIRECTION OF SURFACE |
| WATER FLOW TO A STORM SEWER OR AN APPROVED POINT OF |
| COLLECTION. THE SURFACE WATER CAN NOT BE DIVERTED ONTO |
| THE ADJACENT PROPERTIES. INDICATE HOW IT WILL BE KEPT |
| ON THE LOT AND ROUTED TO THE COLLECTION POINT. |
| |
| 3) THE WALL LEGEND ON A1 INCORRECTLY SPECIFIES 16" |
| RATHER THAN 6" THICK R-19 INSULATION FOR WALLS C, D AND |
| E. PLEASE CORRECT. |
| |
| 4) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE ICYENE INSULATION. |
| |
| 5)THE SPIRAL STAIR DETAIL ON A5 DOES NOT INDICATE THE |
| REQUIRED MINIMUM 26" WIDTH AND THE 7-1/2 " MINIMUM |
| TREAD DEPTH AT 12" FROM THE NARROWER EDGE. SEE FBC |
| R311.5.8.1. SHOP DRAWINGS WILL BE REQUIRED TO BE |
| SUBMITTED FOR APPROVAL PRIOR TO INSTALLATION. |
| |
| 6) THE NOTES ON A1 AND A4 AND SECTION 01 ON S1 DO NOT |
| COMPLY WITH SECTION 704 OF THE FBC. A 4" INSPECTION |
| SPACE IS REQUIRED ABOVE PATIO AND GARAGE SLABS AND |
| ENTRY AREAS PER EXCEPTION (3) . EXCEPTION (4) ALLOWS |
| TERMITE TREATED PATIO SLABS TO MATCH THE INTERIOR |
| FINISH FLOOR ELEVATION ON MASONRY CONSTRUCTION ONLY. |
| EXCEPTION (4) CAN NOT BE USED BECAUSE THE STRUCTURE IS |
| WOOD FRAME. PLEASE REVISE. |
| |
| 7) THE FOOTING SCHEDULE ON S1 IS INCORRECT FOR MARK |
| (A). THE MONOLITHIC FOOTING IS REQUIRED TO BE A MINIMUM |
| OF 18" THICK. FBC 704 REQUIRES A 6" CLEARANCE FOR |
| TERMITE INSPECTION AND FBC R403.1.4 REQUIRES EXTERIOR |
| FOOTERS TO BE 12" BELOW GRADE. ALSO SEE R404.1.6. |
| |
| 8) SECTIONS 03 AND 10 ON S2 CONTAIN CONFLICTING |
| INFORMATION. THE ATTACHMENT OF THE LEDGER TO THE WOOD |
| FRAME WALLS IS SPECIFIED WITH TAPCONS ON ONE AND POWER |
| ACTUATED FASTENERS ON THE OTHER. PLEASE CORRECT. |
| |
| 9) PROVIDE SPECIFICATIONS OR TECHNICAL BULLETION FROM |
| THE MANUFACTURER INDICATING THAT THE LSSH HANGERS CAN |
| BE USED UPSIDE DOWN AND SPECIFY THE DESIGN UPLIFT |
| PRESSURE. SEE SECTION 03 AND 10 ON S2. |
| |
| 10) SPECIFY THE CONNECTOR USED TO ATTACH THE PARAPET |
| WALL TO THE RAFTERS AND WALL BELOW ON S2. SEE RED MARKS |
| ON PLANS. |
| |
| 11)SPECIFY THE WALL TO BEAM CONNECTORS ON SECTIONS 5 |
| AND 6 ON S2. |
| |
| 12) SPECIFY THE LOCATIONS OF THE TDX2 HOLD DOWNS |
| SPECIFIED IN SECTION 12 ON S2. |
| |
| 13) SPECIFY THE SECOND FLOOR WALL TO FIRST FLOOR WALL |
| CONNECTOR IN SECTION 1 ON S2. |
| |
| 14) SECTIONS 3, 10, 11 AND 12 ON S2 INCORRECTLY SPECIFY |
| THE ROOF RAFTERS AS FLOOR JOISTS PLEASE CORRECT. |
| |
| 15) THE PRODUCT APPROVALS FOR THE USP TDX2 AND LSSH |
| CONNECTORS HAVE NOT BEEN SUBMITTED. |
| |
| 16) ALL OF THE PRODUCT APPROVALS ARE REQUIRED TO BE |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC |
| 106.3*. SEE USP PRODUCT APPROVALS. |
| |
| 17) PRODUCT APPROVALS FOR SIMPSON CONNECTORS SUBMITTED |
| ARE NOT APPLICABLE. THERE WERE NO SIMPSON CONNETORS |
| SPECIFIED ON THE PLANS. |
| |
| 18) THE PRODUCT APPROVAL FOR THE SEALOFLEX |
| WATERPROOFING SYSTEM REQUIRES SIGNED AND SEALED RAS 117 |
| CALCULATIONS FROM AN ARCHITECT OR ENGINEER FOR ENHANCED |
| FASTENING. THE LETTER SUBMITTED IS NOT ACCEPTABLE. |
| |
| 19)THE PRODUCT APPROVAL FOR THE TAMKO MODIFIED ROOF |
| SYSTEM REQUIRES SIGNED AND SEALED RAS 117 CALCULATIONS |
| FROM AN ARCHITECT OR ENGINEER FOR ENHANCED FASTENING. |
| THE LETTER SUBMITTED IS NOT ACCEPTABLE. |
| |
| 20) THE UPLIFT PRESSURES ON S3 OF THE PLANS, THE |
| ENGINEERS CALCULATION REPORT AND THE ROOF ENHANCED |
| FASTENING LETTER HAVE DIFFERENT UPLIFTS. PLEASE |
| REVIEW. |
| |
| 21) THE ROOF VERTICAL WINDLOADS (UPLIFT PRESSURES) IN |
| THE ENGINEER'S REPORT APPEAR TO BE TOO LOW FOR 150 MPH |
| EXPOSURE C. PLEASE REVIEW. THE WINDLOAD CALCULATIONS |
| REFERENCE ASCE7-98. THE EDITION OF ASCE7 REFERENCED IN |
| THE 2004 FBC IS ASCE7-02. PLEASE REVISE THE WINDLOAD |
| CALCULATION REPORT. |
| |
| 22) SUBMIT OLD PLAN SHEETS WITH IMPACT FEE STAMP OR |
| HAVE NEW ONES STAMPED BY THE COUNTY. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |