Plan Review Notes
Plan Review Notes For Permit 06110514
Permit Number 06110514
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-05 18:23:26 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} 240.24(B) OCCUPANCY. EACH OCCUPANT SHALL HAVE READY
 ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE
 CONDUCTORS SUPPLYING THAT OCCUPANCY.
  
 2} THE PANEL AT THE GARAGE MUST BE GROUNDED PER 250.32,
 SIZED PER 250.66.
  
 3} THE PANEL AT THE GARAGE MUST CONTAIN A MAIN
 DISCONNECT PER 230.70, LOCATED PER 225.32, OR A
 DISCONNECT MUST BE INSTALLED.
  
 4} VERIFY THAT THE METER ON THE RISER IS A CURRENT
 TRANSFORMER TYPE METER AS THIS IS UNUSUAL FOR A
 RESIDENTIAL SERVICE.THE RISER MUST BE CORRECT OR WILL
 HAVE TO BE RESUBMITTED LATER PROBABLY CAUSING A DELAY
 IN THE JOB PROGRESS.
  
 5} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 6} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 7} THE ENGINEER OF RECORD SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER
 INFORMATION REQUIRED BY 61G15-23.002FLORIDA
 ADMINISTRATIVE CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718