| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} 240.24(B) OCCUPANCY. EACH OCCUPANT SHALL HAVE READY |
| ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE |
| CONDUCTORS SUPPLYING THAT OCCUPANCY. |
| |
| 2} THE PANEL AT THE GARAGE MUST BE GROUNDED PER 250.32, |
| SIZED PER 250.66. |
| |
| 3} THE PANEL AT THE GARAGE MUST CONTAIN A MAIN |
| DISCONNECT PER 230.70, LOCATED PER 225.32, OR A |
| DISCONNECT MUST BE INSTALLED. |
| |
| 4} VERIFY THAT THE METER ON THE RISER IS A CURRENT |
| TRANSFORMER TYPE METER AS THIS IS UNUSUAL FOR A |
| RESIDENTIAL SERVICE.THE RISER MUST BE CORRECT OR WILL |
| HAVE TO BE RESUBMITTED LATER PROBABLY CAUSING A DELAY |
| IN THE JOB PROGRESS. |
| |
| 5} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| |
| 6} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| |
| 7} THE ENGINEER OF RECORD SHALL INDICATE THE |
| CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER |
| INFORMATION REQUIRED BY 61G15-23.002FLORIDA |
| ADMINISTRATIVE CODE. |
| |