2007-01-26 09:10:40DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SHOW COMPLIANCE WITH R401.3 DRAINAGE .
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 3)SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED.
 THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND
 ITS ATTIC AREA BY NOT LESS THAN ? -INCH (12.7 MM)
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES
 BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL
 HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH
 (15.9 MM) TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE
 SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE
 SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY
 NOT LESS THAN ?-INCH (12.7 MM) GYPSUM BOARD OR
 EQUIVALENT.
  
 4) ON SHEET A-1 SEVERAL SECONG FLOOR WALLS ARE
 INCORRECTLY LABELED. SEE MARKS ON PLAN.
  
 5) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 6) SHOW COMPLIANCE WITH R311.5.8.1 SPIRAL STAIRWAYS.
 SPIRAL STAIRWAYS ARE PERMITTED, PROVIDED THE MINIMUM
 WIDTH SHALL BE 26 INCHES (660 MM) WITH EACH TREAD
 HAVING A 7?-INCHES (190 MM) MINIMUM TREAD DEPTH AT 12
 INCHES FROM THE NARROWER EDGE. ALL TREADS SHALL BE
 IDENTICAL, AND THE RISE SHALL BE NO MORE THAN 9? INCHES
 (241 MM). A MINIMUM HEADROOM OF 6 FEET 6 INCHES (1982
 MM) SHALL BE PROVIDED. SUBMIT SHOP DRAWINGS.
  
 7) SHOW COMPLIANCE WITH R312.2 GUARD OPENING
 LIMITATIONS.
 REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED
 FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE
 INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN
 DIAMETER. SUBMIT SHOP DRAWINGS. SHOW ATTACHMENT
 DETAILS.
  
 8)SHOW COMPLIANCE WITH R903.4.1
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS . AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING .
  
 9) R320.7 REQUIRES ROOF DOWNSPOUTS TO DISCHARGE AT
 LEAST 1 FOOT AWAY FROM THE STRUCTURE SIDEWALL. SHOW
 COMPLIANCE.
  
 10) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 11)DETAIL D1 ON SHEET A4 HAS ILLEGIBLE NOTES.
  
 12)INSULATION WILL BE REQUIRED IN THE FLOOR BETWEEN
 THE SECOND STORY LIVING AREA AND THE ADJACENT
 UNCONDITIONED GARAGE PER FBC CHAPTER 13.
  
 13)SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE
 FINISHED GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 14)SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. NOTE:
 18" MONOLITHIC FOOTING WILL BE REQUIRED TO COMPLY WITH
 ITEMS 13 AND 14.
  
 15)PROVIDE DETAILS ON METAL PLATFORM (LANDING) AT THE
 TOP OF THE SPIRAL STAIRS AND HOW IT WILL BE ATTACHED TO
 THE STRUCTURE.
  
 16) R301.1 DESIGN.
 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL
 BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING
 DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS AND
 WIND LOADS AS PRESCRIBED BY THIS CODE. THE CONSTRUCTION
 OF BUILDINGS AND STRUCTURES SHALL RESULT IN A SYSTEM
 THAT PROVIDES A COMPLETE LOAD PATH CAPABLE OF
 TRANSFERRING ALL LOADS FROM THEIR POINT OF ORIGIN
 THROUGH THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION.
 THE CONNECTIONS ON S2 APPEAR TO BE INADEQUATE.
  
 17) SPECIFY THE CONNECTIONS OF THE STEEL BEAMS TO THE
 WOOD FRAMING AT FLOOR JOISTS AND WALL. SEE SECTIONS 02
 AND 05 ON S2.
  
 18)SECTION 03 ON S2 IS NOT DRAWN CORRECTLY. IT IS
 LOCATED ON THE WALL ABOVE THE FRENCH DOORS ON THE
 SECOND FLOOR. SHOW ALL CONNECTIONS. SEE MARKS ON PLAN.
  
 19)PROVIDE A DETAIL SHOWING THE CONNECTIONS FROM THE
 PARAPET WALL TO THE ROOF RAFTERS AND WALL BELOW.
  
 20) SPECIFY THE STRAPS AND HANGERS TO BE USED TO ANCHOR
 THE COVERED TERRACE ROOF.
  
 21)SECTION 7 ON S2 SHOWS A STUD PLATE TIE WELDED TO A
 STEEL COLUMN USED TO ANCHOR THE BEAM SUPPORTING THE
 TERRACE ROOF. THIS IS INADEQUATE.
  
 22)THE TRIPLE 2XGIRDERS ( HEADERS ) SHOWN ON THE
 SECOND FLOOR PLAN ON S2AT SECOND FLOOR ENTRY DO NOT
 HAVE STUDS SHOWN IN THE FRAME WALL BELOW TO SUPPORT
 THEM.
  
 23) NO HOLDDOWN CONNECTORS ARE SPECIFIED AT THE ENDS OF
 SEARS WALLS TO RESIST OVERTURNING.
  
 24)SHEET S4 HAS TYPICAL STRAP INSTALLATION# 596 AND
 597 FOR TRUSSES. HOWEVER THIS PROJECT HAS NO TRUSSES.
 PLEASE REVISE.
  
 25)DETAIL # 213 ON S4 SHOWS AN EXTERIOR WALL ANCHORED
 WITH POWER ACTUATED FASTENERS. THIS IS INADEQUATE FOR A
 140 MPH WINDSPEED. SHOW ANCHOR BOLTS OR OTHER
 ACCEPTABLE CONNECTOR.
  
 26) DETAIL #122ON S4 SPECIFIES ANCHOR BOLTS. PLEASE
 SPECIFY THE REQUIRED LENGTH/ EMBED DEPTH.
  
 27)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. PRODUCT APPROVALS
 SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 28)SHEET A1 SPECIFIES THAT FRENCH DOORS ARE TO PGT
 IMPACT RESISTANT THE PRODUCT APPROVAL SUBMITTED IS NOT
 IMPACT RATED. PLEASE CORRECT. IF NON-IMPACT REVISE PLAN
 AND SUBMIT STORM PLAN PRDUCT APPROVALS AND INSTALLATION
 SCHEDULE.
  
 29)IF MULTIPLE DESIGN PRESSURES ARE LISTED IN THE
 PRODUCT APPROVALS BASED ON GLASS TYPE, SIZE, ETC.,
 CIRCLE THE ITEMS THAT APPLY TO THE PROJECT. CHECK THE
 DESIGN PRESSURES FOR THE PRODUCT WITH THE ONES
 SPECIFIED FOR THE OPENING BY THE DESIGNER TO DETERMINE
 IF THEY ARE ADEQUATE.
  
 30) THE PRODUCT APPROVAL SUBMITTED FOR THE JELD WEN
 DOORS IS NOT COMPLETE, HAS PAGE FROM ANOTHER NOAAND
 ARE NOT CLEAR. THESE SUBMITTALS ARE SCANNED AND KEPT
 FOR PUBLIC RECORD AND NEED TO BE AS CLEAR AS POSSIBLE.
  
 31)SUBMIT PRODUCT APPROVAL INFORMATION FOR THE USP
 CONNECTORS SPECIFIED ON THE PLANS.
  
 32) THE FL COVER SHEET FOR THE AMARR GARAGE DOOR IS FOR
 THE WRONG CODE VERSION. SUBMIT THE ONE FOR THE 2004
 CODE.
  
 33)ON THE PRODUCT APPROVAL FOR THE TAMKO ROOFING,
 CIRCLE THE FASTENING OPTION THAT WILL BE USED ON PAGE
 17.ENHANCED FASTENING WILL BE REQUIRED IN ROOF ZONES
 2 AND 3. SEE LIMITATION NUMBER 7 ON PAGE 20, WHICH
 REQUIRES SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING FROM A FLORIDA REGISTERED ENGINEER,
 ARCHITECT OR REGISTERED ROOF CONSULANT. SUBMIT SIGNED
 AND SEALED CALCULATIONS.
  
 34)PROVIDE DETAILS OF DECORATIVE SUPPORT CHAINS AT
 COVERED TERRACE AND THEIR ATTACHMENTS.
  
 35) SUBMIT MANUFACTURES SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE "SEALOFLEX" WATERPROOFING SYSTEM
 AT THE ROOF TERRACE.
  
 36) FAC 61G15-23.002 REQUIRES ENGINEERS TO LEGIBLY
 INDICATE THEIR ADDRESS ON EACH SHEET. PLEASE COMPLY.
  
 37) ALSO SEE NOTES AND RED MARKS ON THE PLANS.
  
 IN ORDER TO EXPEDITE PLAN REVIEW PLEASE SUBMIT ONE SET
 OF THE OLD PLANS WHEN RESUBMITTING CORRECTED PLANS. DUE
 TO MISSING INFORMATION ADDITIONAL COMMENTS MAY RESULT
 WHEN NEW INFORMATION IS SUBMITTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  