Date |
Text |
2007-01-26 09:10:40 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SHOW COMPLIANCE WITH R401.3 DRAINAGE . |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS |
| TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM |
| OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 |
| MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| |
| 3)SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED. |
| THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND |
| ITS ATTIC AREA BY NOT LESS THAN ? -INCH (12.7 MM) |
| GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES |
| BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL |
| HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH |
| (15.9 MM) TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE |
| SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE |
| SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY |
| NOT LESS THAN ?-INCH (12.7 MM) GYPSUM BOARD OR |
| EQUIVALENT. |
| |
| 4) ON SHEET A-1 SEVERAL SECONG FLOOR WALLS ARE |
| INCORRECTLY LABELED. SEE MARKS ON PLAN. |
| |
| 5) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / |
| 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM |
| OPENINGS. |
| |
| 6) SHOW COMPLIANCE WITH R311.5.8.1 SPIRAL STAIRWAYS. |
| SPIRAL STAIRWAYS ARE PERMITTED, PROVIDED THE MINIMUM |
| WIDTH SHALL BE 26 INCHES (660 MM) WITH EACH TREAD |
| HAVING A 7?-INCHES (190 MM) MINIMUM TREAD DEPTH AT 12 |
| INCHES FROM THE NARROWER EDGE. ALL TREADS SHALL BE |
| IDENTICAL, AND THE RISE SHALL BE NO MORE THAN 9? INCHES |
| (241 MM). A MINIMUM HEADROOM OF 6 FEET 6 INCHES (1982 |
| MM) SHALL BE PROVIDED. SUBMIT SHOP DRAWINGS. |
| |
| 7) SHOW COMPLIANCE WITH R312.2 GUARD OPENING |
| LIMITATIONS. |
| REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED |
| FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE |
| INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT |
| ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN |
| DIAMETER. SUBMIT SHOP DRAWINGS. SHOW ATTACHMENT |
| DETAILS. |
| |
| 8)SHOW COMPLIANCE WITH R903.4.1 |
| WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| SCUPPERS . AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING . |
| |
| 9) R320.7 REQUIRES ROOF DOWNSPOUTS TO DISCHARGE AT |
| LEAST 1 FOOT AWAY FROM THE STRUCTURE SIDEWALL. SHOW |
| COMPLIANCE. |
| |
| 10) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR |
| TERMITES. |
| IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS: |
| 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS |
| THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| MASONRY FOUNDATION SIDEWALL. |
| 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE |
| INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH |
| RAMPS ONLY. |
| 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO |
| AND GARAGE SLABS AND ENTRY AREAS. |
| 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, |
| THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR |
| FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY. |
| 5.MASONRY VENEERS. |
| |
| 11)DETAIL D1 ON SHEET A4 HAS ILLEGIBLE NOTES. |
| |
| 12)INSULATION WILL BE REQUIRED IN THE FLOOR BETWEEN |
| THE SECOND STORY LIVING AREA AND THE ADJACENT |
| UNCONDITIONED GARAGE PER FBC CHAPTER 13. |
| |
| 13)SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE |
| FINISHED GRADE. |
| CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| ELSEWHERE. |
| |
| 14)SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL |
| EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES |
| (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. NOTE: |
| 18" MONOLITHIC FOOTING WILL BE REQUIRED TO COMPLY WITH |
| ITEMS 13 AND 14. |
| |
| 15)PROVIDE DETAILS ON METAL PLATFORM (LANDING) AT THE |
| TOP OF THE SPIRAL STAIRS AND HOW IT WILL BE ATTACHED TO |
| THE STRUCTURE. |
| |
| 16) R301.1 DESIGN. |
| BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL |
| BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING |
| DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS AND |
| WIND LOADS AS PRESCRIBED BY THIS CODE. THE CONSTRUCTION |
| OF BUILDINGS AND STRUCTURES SHALL RESULT IN A SYSTEM |
| THAT PROVIDES A COMPLETE LOAD PATH CAPABLE OF |
| TRANSFERRING ALL LOADS FROM THEIR POINT OF ORIGIN |
| THROUGH THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION. |
| THE CONNECTIONS ON S2 APPEAR TO BE INADEQUATE. |
| |
| 17) SPECIFY THE CONNECTIONS OF THE STEEL BEAMS TO THE |
| WOOD FRAMING AT FLOOR JOISTS AND WALL. SEE SECTIONS 02 |
| AND 05 ON S2. |
| |
| 18)SECTION 03 ON S2 IS NOT DRAWN CORRECTLY. IT IS |
| LOCATED ON THE WALL ABOVE THE FRENCH DOORS ON THE |
| SECOND FLOOR. SHOW ALL CONNECTIONS. SEE MARKS ON PLAN. |
| |
| 19)PROVIDE A DETAIL SHOWING THE CONNECTIONS FROM THE |
| PARAPET WALL TO THE ROOF RAFTERS AND WALL BELOW. |
| |
| 20) SPECIFY THE STRAPS AND HANGERS TO BE USED TO ANCHOR |
| THE COVERED TERRACE ROOF. |
| |
| 21)SECTION 7 ON S2 SHOWS A STUD PLATE TIE WELDED TO A |
| STEEL COLUMN USED TO ANCHOR THE BEAM SUPPORTING THE |
| TERRACE ROOF. THIS IS INADEQUATE. |
| |
| 22)THE TRIPLE 2XGIRDERS ( HEADERS ) SHOWN ON THE |
| SECOND FLOOR PLAN ON S2AT SECOND FLOOR ENTRY DO NOT |
| HAVE STUDS SHOWN IN THE FRAME WALL BELOW TO SUPPORT |
| THEM. |
| |
| 23) NO HOLDDOWN CONNECTORS ARE SPECIFIED AT THE ENDS OF |
| SEARS WALLS TO RESIST OVERTURNING. |
| |
| 24)SHEET S4 HAS TYPICAL STRAP INSTALLATION# 596 AND |
| 597 FOR TRUSSES. HOWEVER THIS PROJECT HAS NO TRUSSES. |
| PLEASE REVISE. |
| |
| 25)DETAIL # 213 ON S4 SHOWS AN EXTERIOR WALL ANCHORED |
| WITH POWER ACTUATED FASTENERS. THIS IS INADEQUATE FOR A |
| 140 MPH WINDSPEED. SHOW ANCHOR BOLTS OR OTHER |
| ACCEPTABLE CONNECTOR. |
| |
| 26) DETAIL #122ON S4 SPECIFIES ANCHOR BOLTS. PLEASE |
| SPECIFY THE REQUIRED LENGTH/ EMBED DEPTH. |
| |
| 27)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. PRODUCT APPROVALS |
| SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. |
| |
| 28)SHEET A1 SPECIFIES THAT FRENCH DOORS ARE TO PGT |
| IMPACT RESISTANT THE PRODUCT APPROVAL SUBMITTED IS NOT |
| IMPACT RATED. PLEASE CORRECT. IF NON-IMPACT REVISE PLAN |
| AND SUBMIT STORM PLAN PRDUCT APPROVALS AND INSTALLATION |
| SCHEDULE. |
| |
| 29)IF MULTIPLE DESIGN PRESSURES ARE LISTED IN THE |
| PRODUCT APPROVALS BASED ON GLASS TYPE, SIZE, ETC., |
| CIRCLE THE ITEMS THAT APPLY TO THE PROJECT. CHECK THE |
| DESIGN PRESSURES FOR THE PRODUCT WITH THE ONES |
| SPECIFIED FOR THE OPENING BY THE DESIGNER TO DETERMINE |
| IF THEY ARE ADEQUATE. |
| |
| 30) THE PRODUCT APPROVAL SUBMITTED FOR THE JELD WEN |
| DOORS IS NOT COMPLETE, HAS PAGE FROM ANOTHER NOAAND |
| ARE NOT CLEAR. THESE SUBMITTALS ARE SCANNED AND KEPT |
| FOR PUBLIC RECORD AND NEED TO BE AS CLEAR AS POSSIBLE. |
| |
| 31)SUBMIT PRODUCT APPROVAL INFORMATION FOR THE USP |
| CONNECTORS SPECIFIED ON THE PLANS. |
| |
| 32) THE FL COVER SHEET FOR THE AMARR GARAGE DOOR IS FOR |
| THE WRONG CODE VERSION. SUBMIT THE ONE FOR THE 2004 |
| CODE. |
| |
| 33)ON THE PRODUCT APPROVAL FOR THE TAMKO ROOFING, |
| CIRCLE THE FASTENING OPTION THAT WILL BE USED ON PAGE |
| 17.ENHANCED FASTENING WILL BE REQUIRED IN ROOF ZONES |
| 2 AND 3. SEE LIMITATION NUMBER 7 ON PAGE 20, WHICH |
| REQUIRES SIGNED AND SEALED RAS 117 CALCULATIONS FOR |
| ENHANCED FASTENING FROM A FLORIDA REGISTERED ENGINEER, |
| ARCHITECT OR REGISTERED ROOF CONSULANT. SUBMIT SIGNED |
| AND SEALED CALCULATIONS. |
| |
| 34)PROVIDE DETAILS OF DECORATIVE SUPPORT CHAINS AT |
| COVERED TERRACE AND THEIR ATTACHMENTS. |
| |
| 35) SUBMIT MANUFACTURES SPECIFICATIONS AND INSTALLATION |
| INSTRUCTIONS FOR THE "SEALOFLEX" WATERPROOFING SYSTEM |
| AT THE ROOF TERRACE. |
| |
| 36) FAC 61G15-23.002 REQUIRES ENGINEERS TO LEGIBLY |
| INDICATE THEIR ADDRESS ON EACH SHEET. PLEASE COMPLY. |
| |
| 37) ALSO SEE NOTES AND RED MARKS ON THE PLANS. |
| |
| IN ORDER TO EXPEDITE PLAN REVIEW PLEASE SUBMIT ONE SET |
| OF THE OLD PLANS WHEN RESUBMITTING CORRECTED PLANS. DUE |
| TO MISSING INFORMATION ADDITIONAL COMMENTS MAY RESULT |
| WHEN NEW INFORMATION IS SUBMITTED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |
| |
| |