2006-11-28 16:01:42 | *** DENIED *** |
| 1) DUE TO THE 1000 GAL. FUEL TANK THE PLANS NEED TO BE |
| APPROVED BY THE FL. DEPT. OF ENVIRONMENTAL PROTECTION |
| (2300 N. JOG RD. W.P.B. (561) 233-2400) BEFORE APPLYING |
| FOR PERMIT. |
| |
| 2) INFORMATIONAL ONLY. PER 2004 FBC, FUEL GAS - |
| POWERED |
| EQUIPMENT - PERMANENTLY INSTALLED |
| EQUIPMENT POWERED BY INTERNAL COMBUSTION |
| ENGINES SHALL BE INSTALLED IN ACCORDANCE |
| WITH MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS AND NFPA 37. |
| |
| NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION |
| ENGINES & GAS TURBINES: |
| 4.1.4ENGINES (GENERATORS) LOCATED |
| OUTDOORS SHALL BE MINIMUM OF 5 FT FROM |
| OPENINGS IN WALLS & AT LEAST 5 FT FROM |
| STRUCTURES HAVING COMBUSTIBLE WALLS.A |
| MINIMUM CLEARANCE IS NOT REQUIRED WHEN |
| (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE |
| RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS |
| CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS |
| BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| MATERIALS OUTSIDE THE ENCLOSURE. |
| INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS |
| SHOULD NOT TERMINATE UNDER STRUCTURES OR |
| WHERE THE EXHAUST MIGHT BE DRAWN INTO |
| THE VENTILATION INTAKES. |
| |
| GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE |
| MENTIONED CLEARANCES TO THE ADJACENT |
| PROPERTY STRUCTURES, I.E. FENCE, |
| BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| |
| FUEL STORAGE TANK MUST BE A MINIMUM DISTANCE OF 5 FEET |
| FROM BUILDING, SEE NFPA 30 CH. 4, 4.3.2.1.1. |
| |
| FOLLOW MANUFACTURER'S RECOMMENDED |
| CLEARANCES AROUND EQUIPMENT FOR |
| SERVICING,AND PROVIDE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS AT THE JOBSITE |
| FOR THE FIELD INSPECTOR. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |