Plan Review Notes For Permit 06110497 |
Permit Number |
06110497 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-04 21:25:54 | *****DENIED***** | | | | | | | | 1.CONSTRUCTION AND/OR DEMOLITION OPERATIONS IN OR | | AROUND THE AREA OF WORK SHALL NOT INTERFERE WITH | | EMERGENCY RESPONSE ACCESS TO THE BUILDING(S) OR THE | | VICINITY THEREOF (INCLUDING FIRE LANES). | | | | 2.PLEASE DESCRIBE ANY AND ALL LIFE SAFETY EQUIPMENT | | PLANNED TO BE SUPPLIED BY THE GENERATOR. | | | | 3.STATIONARY GENERATORS USED FOR EMERGENCY OR STANDBY | | POWER SHALL BE INSTALLED, TESTED, MAINTAINED, AND | | COMPLY WITH NFPA 110. | | | | 4.DIESEL FUEL STORAGE SHALL COMPLY WITH NFPA 30. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | 4. |
|