Plan Review Notes
Plan Review Notes For Permit 06110497
Permit Number 06110497
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-04 21:25:54*****DENIED*****
  
  
  
 1.CONSTRUCTION AND/OR DEMOLITION OPERATIONS IN OR
 AROUND THE AREA OF WORK SHALL NOT INTERFERE WITH
 EMERGENCY RESPONSE ACCESS TO THE BUILDING(S) OR THE
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 2.PLEASE DESCRIBE ANY AND ALL LIFE SAFETY EQUIPMENT
 PLANNED TO BE SUPPLIED BY THE GENERATOR.
  
 3.STATIONARY GENERATORS USED FOR EMERGENCY OR STANDBY
 POWER SHALL BE INSTALLED, TESTED, MAINTAINED, AND
 COMPLY WITH NFPA 110.
  
 4.DIESEL FUEL STORAGE SHALL COMPLY WITH NFPA 30.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW