2006-12-06 19:43:36 | ***********UNSAT ************* |
| |
| PUBLIX GENERATOR |
| #651 |
| |
| 1) NOTE:PLEASE SEE VALUE FOR SCOPE AHS BEEN INCREASED |
| TO THE COST OF OTHER TYPICAL GENERATORS APPLIED FOR IN |
| THIS JURISDICTION.PLEASE KNOW FALSIFYING INFORMATION |
| ON AN APPLICATION IS GROUNDS FOR TURNING OVER TO THE |
| STATE ECLB. PLEASE KNOW THIS COMMENT HAS BEEN MADE ON |
| ALL OTHER PROJECTS SUBMITTED BY THIS CONTRACTOR FOR THE |
| SAME SCOPE OF WORK AND THIS IS STILL BEING SUBMITTED |
| WITH VALUES WAY LOW FOR ANY LABOR OR MATERIALS. PLEASE |
| KNOW ANY FUTURE PROJECTS WILL NOT BE PROCESSED OR |
| REVIEWED IF THIS IS DONE. THIS HAS NOW BEEN DOCUMENTED |
| AS THE FOURTH PROJECT LOCATED IN THE CITY OF WEST PALM |
| BEACH WHERE THE APPLICATIONS HAVE BEEN SUBMITTED BELOW |
| ANY LEVELS OF VALUE ACCURATE TO THE SCOPE OF WORK. |
| THE VALUE OF $10K ON PERMIT APPLICATION SUBMITTED IS |
| EXTREMELY LOW. |
| PLEASE KNOW THAT VALUE SHALL BE ALL LABOR AND MATERIALS |
| EVEN IF MATERIALS ARE OWNER SUPPLIED.PLEASE SEE FBC |
| 2004, ADMINISTRATIVE CODE SECTION 108.3 AS ADOPTED BY |
| THE CITY OF WEST PALM BEACH. |
| PLEASE KNOW, UNDER CONTRACTING LAWS AND RULES SET UP |
| AND ADOPTED INTO FLORIDA |
| STATUTES, 489, FBC ADMINISTRATIVE SECTION |
| 105.5.1 ANY INFORMATION PROVIDED ON OFFICIAL PERMIT |
| APPLICATION IF KNOWINGLY BEING FALSIFIED CAN |
| VOID/REVOKE SUCH PERMIT/ APPLICATION. |
| ** PLEASE KNOW THESE FEES OF $1975.80 ARE DUE AT THIS |
| TIME AND WILL BE REQUIRED TO BE PAID BEFORE PICKING UP |
| PLANS. NO EXCEPTIONS. |
| |
| 2) NOTE: PLEASE KNOW, ANY SYSTEMS LOCATED IN A FLOOD |
| ZONE "A" WILL BE REQUIRED TO BE MOUNTED AT A MIN OF 6" |
| ABOVE BFE. PLEASE SEE BUILDING REVIEW COMMENTS. |
| |
| 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE CUT SHEETS. |
| APS/ ATS DO NOT INDICATE THE REQUIRED MEANS OF |
| DISCONNECT AS REQUIRED BY 230.76,230.79, 225.31-39. |
| PLEASE SEE A MANUAL MEANS OF DISCONNECT COULD NOT BE |
| LOCATED RATED FOR THE LOAD SERVED ON THE OUTSIDE OF |
| EQUIPMENT SUBMITTED. |
| THIS WAS NEVER VERIFIED FROM PREVIOUS PERMIT PULLED FOR |
| PREVIOUS PROJECT. |
| NO PERMITS WILL BE RELEASED UNLESS THIS IS VERIFIED ON |
| ALL SUBMITTED SPECS AND PLANS SUBMITTED BEFORE PERMIT |
| IS ISSUED. |
| PLEASE SEE ALL EQUIPMENT SHALL BE LISTED FOR USE.90.7, |
| 110.3 |
| |
| 4) NOTE: PLEASE INDICATE THE OCP AT THE GEN. PLEASE SEE |
| 445.13 AS IT HAS COME TO OUR ATTENTION ON A PREVIOUS |
| PROJECT THAT THE GEN MAY NOT CONTAIN OCP AND CAN NOT BE |
| VERIFIED AT THIS TIME. |
| |
| 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED |
| FOR REVIEW. PLEASE SUBMIT. |
| PLEASE SUBMIT AND INDICATE ANY LOAD SHEDDING DETAILS IF |
| APPLICABLE. |
| 702.5, 220 |
| |
| 6) NOTE: PLEASE PROVIDE INFORMATION IF THE GEN WILL BE |
| FEEDING ANY "LEGALLY REQUIRED STAND-BY SYSTEMS". PLANS |
| TO INDICATE THIS, NOT ONLY IN A RESPONSE LETTER. |
| |
| 7) NOTE:PLEASE SEE PLANS SHALL INDICATE THE CURRENT |
| CODES IN EFFECT FOR INSTALLATION AS FOLLOWS. PLEASE SEE |
| FBC 2004 CHAPTER 27FOR ADOPTED CODES RELEVANT TO |
| POWER GENERATORS. |
| 2002 NFPA-70, 2002 NFPA-110(WHERE CLASS 1 OR 2) |
| |
| 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| SHEETS FOR THE GENERATOR. NONE SUBMITTED AT THIS TIME, |
| UNABLE TO REVIEW. |
| 110.3, 90.7. ETC |
| FCB 106.1.2 |
| |
| 9) NOTE: PLEASE SEE THE APS/ATS IS BECOMING THE NEW |
| FIRST MEANS OF DISCONNECT HOWEVER THE NEW GROUNDING |
| ELECTRODE SYSTEMS DOES NOT SEEM TO BE COMPLETE AS PER |
| 250.50. |
| PLEASE SEE GROUNDING DETAIL MENTIONS NEW SLAB STEEL |
| WHICH IS OK, HOWEVER PLEASE INDICATE ATTACHMENT. |
| THESE NEW SLAB/STEEL ATTACHMENTS DO NOT MEET THE MIN |
| REQUIREMENTS PER |
| 250.50, 250.52, 250.104 |
| IF SLAB STEEL IS ONLY BEING BONDED, THEN PLEASE |
| INDICATE. |
| PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AND |
| BONDING FOR ALL AS ABOVE. |
| PLEASE SEE DETAIL STILL INDICATES THE NEUTRAL AND |
| EXISTING GROUNDING ELECTRODE SYSTEM BEING BONDED AT THE |
| EXISTING SERVICE WHICH WILL PARALLEL THE NEW SYSTEM |
| REQUIRED. |
| 250.6, 250.24B. |
| |
| 10) NOTE: PLEASE SEE SETS OF CONDUITS AND FEEDERS DO |
| NOT SEEM TO INDICATE THE NEW REQUIRED "EQUIPMENT |
| GROUNDING CONDUCTOR" TO THE EXISTING MAINS. THESE ARE |
| NO LONGER THE FIRST MEANS OF DISCONNECT. |
| 250.110,250.122,250.24B, 250.6, AS NOTED ABOVE IN NOTE |
| #9 |
| |
| 11) NOTE:PLEASE KNOW, BASED ON ALL PREVIOUS PROJECTS, |
| IS THIS UNIT GOING TO BE "BI-FUEL"?? |
| IF SO, SUBMIT ALL INFORMATION AND SPECS ON UNIT(S). |
| 90.7, 110.3 |
| |
| 12) NOTE: PLEASE KNOW AS THE ORIGINAL PROJECT AT STORE |
| #50 LOCATED AT 828 SOUTHERN BLVD HAS NOT PASSED |
| INSPECTIONS AND THERE ARE SEVERAL UNANSWERED QUESITONS |
| ON PROJECT,AS STATED ON OTHER GENERATOR PERMITS, |
| THESE WILL NOT BE ISSUED UNTIL ALL CODE COMPLIANCE IS |
| MET ON THE ORIGINAL PROJECT. |
| PLEASE KNOW ALL PERMITS EXPIRE WITHIN 6 MONTHS OF IN- |
| ACTIVITY. |
| FBC ADMIN SECTION 105.3.2 |
| |
| |
| ** PLEASE KNOW, AS MUCH INFORMATION WAS NOT SUBMITTED, |
| A COMPLETE REVIEW COULD NOT BE DONE. |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |