Plan Review Notes
Plan Review Notes For Permit 06110497
Permit Number 06110497
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-06 19:43:36***********UNSAT *************
  
 PUBLIX GENERATOR
 #651
  
 1) NOTE:PLEASE SEE VALUE FOR SCOPE AHS BEEN INCREASED
 TO THE COST OF OTHER TYPICAL GENERATORS APPLIED FOR IN
 THIS JURISDICTION.PLEASE KNOW FALSIFYING INFORMATION
 ON AN APPLICATION IS GROUNDS FOR TURNING OVER TO THE
 STATE ECLB. PLEASE KNOW THIS COMMENT HAS BEEN MADE ON
 ALL OTHER PROJECTS SUBMITTED BY THIS CONTRACTOR FOR THE
 SAME SCOPE OF WORK AND THIS IS STILL BEING SUBMITTED
 WITH VALUES WAY LOW FOR ANY LABOR OR MATERIALS. PLEASE
 KNOW ANY FUTURE PROJECTS WILL NOT BE PROCESSED OR
 REVIEWED IF THIS IS DONE. THIS HAS NOW BEEN DOCUMENTED
 AS THE FOURTH PROJECT LOCATED IN THE CITY OF WEST PALM
 BEACH WHERE THE APPLICATIONS HAVE BEEN SUBMITTED BELOW
 ANY LEVELS OF VALUE ACCURATE TO THE SCOPE OF WORK.
 THE VALUE OF $10K ON PERMIT APPLICATION SUBMITTED IS
 EXTREMELY LOW.
 PLEASE KNOW THAT VALUE SHALL BE ALL LABOR AND MATERIALS
 EVEN IF MATERIALS ARE OWNER SUPPLIED.PLEASE SEE FBC
 2004, ADMINISTRATIVE CODE SECTION 108.3 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 PLEASE KNOW, UNDER CONTRACTING LAWS AND RULES SET UP
 AND ADOPTED INTO FLORIDA
 STATUTES, 489, FBC ADMINISTRATIVE SECTION
 105.5.1 ANY INFORMATION PROVIDED ON OFFICIAL PERMIT
 APPLICATION IF KNOWINGLY BEING FALSIFIED CAN
 VOID/REVOKE SUCH PERMIT/ APPLICATION.
 ** PLEASE KNOW THESE FEES OF $1975.80 ARE DUE AT THIS
 TIME AND WILL BE REQUIRED TO BE PAID BEFORE PICKING UP
 PLANS. NO EXCEPTIONS.
  
 2) NOTE: PLEASE KNOW, ANY SYSTEMS LOCATED IN A FLOOD
 ZONE "A" WILL BE REQUIRED TO BE MOUNTED AT A MIN OF 6"
 ABOVE BFE. PLEASE SEE BUILDING REVIEW COMMENTS.
  
 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE CUT SHEETS.
 APS/ ATS DO NOT INDICATE THE REQUIRED MEANS OF
 DISCONNECT AS REQUIRED BY 230.76,230.79, 225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT COULD NOT BE
 LOCATED RATED FOR THE LOAD SERVED ON THE OUTSIDE OF
 EQUIPMENT SUBMITTED.
 THIS WAS NEVER VERIFIED FROM PREVIOUS PERMIT PULLED FOR
 PREVIOUS PROJECT.
 NO PERMITS WILL BE RELEASED UNLESS THIS IS VERIFIED ON
 ALL SUBMITTED SPECS AND PLANS SUBMITTED BEFORE PERMIT
 IS ISSUED.
 PLEASE SEE ALL EQUIPMENT SHALL BE LISTED FOR USE.90.7,
 110.3
  
 4) NOTE: PLEASE INDICATE THE OCP AT THE GEN. PLEASE SEE
 445.13 AS IT HAS COME TO OUR ATTENTION ON A PREVIOUS
 PROJECT THAT THE GEN MAY NOT CONTAIN OCP AND CAN NOT BE
 VERIFIED AT THIS TIME.
  
 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT.
 PLEASE SUBMIT AND INDICATE ANY LOAD SHEDDING DETAILS IF
 APPLICABLE.
 702.5, 220
  
 6) NOTE: PLEASE PROVIDE INFORMATION IF THE GEN WILL BE
 FEEDING ANY "LEGALLY REQUIRED STAND-BY SYSTEMS". PLANS
 TO INDICATE THIS, NOT ONLY IN A RESPONSE LETTER.
  
 7) NOTE:PLEASE SEE PLANS SHALL INDICATE THE CURRENT
 CODES IN EFFECT FOR INSTALLATION AS FOLLOWS. PLEASE SEE
 FBC 2004 CHAPTER 27FOR ADOPTED CODES RELEVANT TO
 POWER GENERATORS.
 2002 NFPA-70, 2002 NFPA-110(WHERE CLASS 1 OR 2)
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR. NONE SUBMITTED AT THIS TIME,
 UNABLE TO REVIEW.
 110.3, 90.7. ETC
 FCB 106.1.2
  
 9) NOTE: PLEASE SEE THE APS/ATS IS BECOMING THE NEW
 FIRST MEANS OF DISCONNECT HOWEVER THE NEW GROUNDING
 ELECTRODE SYSTEMS DOES NOT SEEM TO BE COMPLETE AS PER
 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW SLAB STEEL
 WHICH IS OK, HOWEVER PLEASE INDICATE ATTACHMENT.
 THESE NEW SLAB/STEEL ATTACHMENTS DO NOT MEET THE MIN
 REQUIREMENTS PER
 250.50, 250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED, THEN PLEASE
 INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AND
 BONDING FOR ALL AS ABOVE.
 PLEASE SEE DETAIL STILL INDICATES THE NEUTRAL AND
 EXISTING GROUNDING ELECTRODE SYSTEM BEING BONDED AT THE
 EXISTING SERVICE WHICH WILL PARALLEL THE NEW SYSTEM
 REQUIRED.
 250.6, 250.24B.
  
 10) NOTE: PLEASE SEE SETS OF CONDUITS AND FEEDERS DO
 NOT SEEM TO INDICATE THE NEW REQUIRED "EQUIPMENT
 GROUNDING CONDUCTOR" TO THE EXISTING MAINS. THESE ARE
 NO LONGER THE FIRST MEANS OF DISCONNECT.
 250.110,250.122,250.24B, 250.6, AS NOTED ABOVE IN NOTE
 #9
  
 11) NOTE:PLEASE KNOW, BASED ON ALL PREVIOUS PROJECTS,
 IS THIS UNIT GOING TO BE "BI-FUEL"??
 IF SO, SUBMIT ALL INFORMATION AND SPECS ON UNIT(S).
 90.7, 110.3
  
 12) NOTE: PLEASE KNOW AS THE ORIGINAL PROJECT AT STORE
 #50 LOCATED AT 828 SOUTHERN BLVD HAS NOT PASSED
 INSPECTIONS AND THERE ARE SEVERAL UNANSWERED QUESITONS
 ON PROJECT,AS STATED ON OTHER GENERATOR PERMITS,
 THESE WILL NOT BE ISSUED UNTIL ALL CODE COMPLIANCE IS
 MET ON THE ORIGINAL PROJECT.
 PLEASE KNOW ALL PERMITS EXPIRE WITHIN 6 MONTHS OF IN-
 ACTIVITY.
 FBC ADMIN SECTION 105.3.2
  
  
 ** PLEASE KNOW, AS MUCH INFORMATION WAS NOT SUBMITTED,
 A COMPLETE REVIEW COULD NOT BE DONE.
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]