Plan Review Notes
Plan Review Notes For Permit 06110497
Permit Number 06110497
Review Stop B
Sequence Number 1
Notes
Date Text
2006-12-20 18:53:02BUILDING PLAN REVIEW
 PERMIT:06110497
 ADD:10130 NORTHLAKE BLVD. #651
 CONT:POWER SECURE INC.
 TEL: (866)347-5455
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW : 1ST
 ACTION: DENIED
  
 1) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2)SHOW CLEARLY ON THE DRAWINGS THE DISTANCE THE
 GENERATOR WILL BE INSTALLED FROM THE BUILDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  