Date |
Text |
2006-12-01 10:29:05 | UNSAT |
| REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE SUBMITTED DRAWINGS ARE NOT AN ISOMETRIC |
| DRAWING AND DO NOT CLEARLY SHOW ALL CUT SECTIONS OF |
| PIPE AND CORRESPONDING LENGTHS. THE ONLY CORRESPONDING |
| LENGTH INDICATED IS THE UNDERGROUND PE. THE ABOVE |
| GROUND CORRESPONDING LENGTHS MUST ALSO BE INDICATED ON |
| DRAWINGS AS WELL AS THE TWO UNDER GROUND TANKS AND HOW |
| THE TANKS WILL BE PIPED AND THE LOCATION OF THE FIRST |
| AND SECOND STAGE REGULATORS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: PLEASE INDICATE THE ABOVE GROUND PIPING MATERIAL |
| AND SIZES. |
| |
| 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 |
| NOTE: PLEASE SUBMIT MANUFACTURE SHEETS OF POOL HEATER. |
| THE MASTER PERMIT NUMBER INDICATED ON THE PERMIT |
| APPLICATION IS CLOSED AND THERE IS NO RECORD ON FILE OF |
| THE POOL HEATER. |
| |
| 4. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| NOTE: THE SUBMITTED SITE DRAWINGS INDICATE ONE UNDER |
| GROUND TANK,BUT THE PERMIT APPLICATION INDICATES TWO |
| UNDERGROUND TANKS. PLEASE CORRELATE THE TWO FOR THE |
| RESUBMITTAL. THERE IS NO INDICATION OF THE TANK TYPE |
| (DOT OR ASME) IN THE SUBMITTALS. PLEASE CORRECT THIS IN |
| THE RESUBMITTAL. |
| |
| 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |