2006-12-01 10:29:05UNSAT
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWINGS ARE NOT AN ISOMETRIC
 DRAWING AND DO NOT CLEARLY SHOW ALL CUT SECTIONS OF
 PIPE AND CORRESPONDING LENGTHS. THE ONLY CORRESPONDING
 LENGTH INDICATED IS THE UNDERGROUND PE. THE ABOVE
 GROUND CORRESPONDING LENGTHS MUST ALSO BE INDICATED ON
 DRAWINGS AS WELL AS THE TWO UNDER GROUND TANKS AND HOW
 THE TANKS WILL BE PIPED AND THE LOCATION OF THE FIRST
 AND SECOND STAGE REGULATORS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: PLEASE INDICATE THE ABOVE GROUND PIPING MATERIAL
 AND SIZES.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE SUBMIT MANUFACTURE SHEETS OF POOL HEATER.
 THE MASTER PERMIT NUMBER INDICATED ON THE PERMIT
 APPLICATION IS CLOSED AND THERE IS NO RECORD ON FILE OF
 THE POOL HEATER.
  
 4. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 NOTE: THE SUBMITTED SITE DRAWINGS INDICATE ONE UNDER
 GROUND TANK,BUT THE PERMIT APPLICATION INDICATES TWO
 UNDERGROUND TANKS. PLEASE CORRELATE THE TWO FOR THE
 RESUBMITTAL. THERE IS NO INDICATION OF THE TANK TYPE
 (DOT OR ASME) IN THE SUBMITTALS. PLEASE CORRECT THIS IN
 THE RESUBMITTAL.
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721