Plan Review Notes For Permit 06110421 |
Permit Number |
06110421 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-09 13:39:33 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB | | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)ENGINEERED PLANS REQUIRED FOR THE EXTERIOR WALLS | | (WALL PANELS WITH FRENCH DOORS AND HORIZONTAL SLIDING | | WINDOWS). | | | | 2.)PROVIDE WIND DESIGN CRITERIA FBC1603.1.4. | | | | 3.)THE PANEL TEST WAS DONE IN 1995 (NOT TO CURRENT | | CODE) AND IS NOT AN EVALUATION REPORT.FLORIDA STATE | | OR LOCAL PRODUCT APPROVAL REQUIRED, FAC9B72. | | | | 4.)THIS WORK IS NOT WITHIN THE SCOPE OF A | | GLASS/GLAZING CONTRACTOR.SEE | | WWW.PBCGOV.COM/PZB/CONTRACTORS, STANDARDS. | | | | 5.)THE PRODUCT APPROVALS DO NOT ADDRESS ANCHORING | | INTO METAL.ADDRESS. | | | | 6.)ARE THE DOUBLE LINES SLIDING GLASS DOORS?IT | | APPEARS THAT THE PORCH IS EMERGENCY MEANS OF EGRESS FOR | | TWO BEDROOMS.YOU CANNOT REDUCE THE SAFETY, FBC EB | | 501.2.PROVIDE INFORMATION IN REGARDS TO THE BEDROOM | | WINDOWS. | | | | 7.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. | | | | 8.)PROVIDE A SITE PLAN SHOWING THE DISTANCE FROM THE | | PROPERTY LINE, FBC R302. | | | | |
|