Plan Review Notes
Plan Review Notes For Permit 06110401
Permit Number 06110401
Review Stop Z
Sequence Number 1
Notes
Date Text
2006-11-16 07:13:33DENIED,
 1. PLEASE PROVIDE THE HOA APPROVAL FOR THE PROPOSED
 GENERATOR AND GAS TANK WITHIN THE FRONT SETBACK.
 2. PLEASE PROVIDE THE DISTANCE OF THE PROPOSED
 GENERATOR AND GAS TANK FROM THE FRONT PROPERTY LINE.
 3. PLEASE PROVIDE ALL THE UTITILTY EASEMENT RELEASES
 FOR THE 12FT UTILITY EASEMENT. THE PROPOSED
 GENERATOR/GAS TANK WILL ENROACH IN THE 12 U.E BASE ON
 THE REQUIRED GUIDELINES.
 4. THE PROPOSED GENERATOR SHALL NOT BE CLOSER THAN 11FT
 FROM CORNER SIDE PROPERTY LINE.
 5. THE PROPOSED GAS TANK SHALL NOT BE CLOSER THAN 16FT
 FROM FRONT PROPERTY LINE AND 11FT FROM THE SIDE
 PROPERTY LINE.
 6. THE PROPOSED GENERATOR MUST BE SCREENED WITH A
 LANDSCAPE BUFFER FROM VIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720