Plan Review Notes
Plan Review Notes For Permit 06110392
Permit Number 06110392
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-30 15:25:58 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE PROVIDE A FLOOR PLAN LOCATING THE EQUIPMENT
 TO BE ADDED, AND EXISTIONG EQUIPMENT AT THE SAME
 LOCATION SO THAT A REVIEW CAN BE MADE TO DETERMINE
 COMPLIANCE WITH 110.26INDICATE FIRE RATED WALLS,
 FLOORS OR OTHER ITEMS PENETRATED BY THE CONDUITS.
  
 2} PROVIDE A LOAD CALCULATION FOR THE EXISTING 400 AMP
 PANEL THAT FEEDS THE NEW EQUIPMENT. INDICATE EXISTING
 LOADS AND THE ADDED TRANSFORMER LOAD. 215.5 NEC.
  
 3} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 4} PLEASE PROVIDE A PANEL SCHEDULE AND DESIGNATION FOR
 THE 200 AMP PANEL BEING ADDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  