2008-10-08 08:04:58REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P2.31 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED.
 PLEASE USE THE SIGNATURE REQUIRED. FS 471.025.
  
 2. SHT P2.31 SHOWS A HOSE BIBB IN THE METER ROOM. NO
 FLOOR DRAIN IS INDICATED. PLEASE SHOW COMPLIANCE WITH
 SECTION 301.2 WHICH STATES THAT PLUMBING SHALL BE
 INSTALLED WITH DUE REGARD TO PRESERVATION OF THE
 STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE
 TO WALLS AND OTHER SURFACES THROUGH FIXTURE USEAGE.
  
 3. SHT P2.31 SHOWS THE 3" VTR BEING CHANGED TO AN AIR
 ADMITTANCE VALVE. SECTION 903.1 REQUIRES AT LEAST ONE
 VENT STACK THE SIZE OF WHICH IS NOT LESS THAN 1/2 OF
 THE REQUIRED SIZE OF THE BUILDING DRAIN TO RUN
 UNDIMINISHED IN SIZE AND DIRECTLY AS POSSIBLE FROM THE
 BUILDING DRAIN THROUGH TO THE OPEN AIR OR TO A VENT
 HEADER THAT EXTENDS TO THE OPEN AIR. PLEASE INDICATE
 HOW THIS WILL BE COMPLIED WITH.
  
 4. SHT P2.31 INDICATES A REVISION #10 ON THE FLOOR
 PLAN. REVISION #10 IS NOT INDICATED ON THE REVISION
 INDEX IN THE TITLE BLOCK. PLEASE CORRELATE. SECTION
 106.1.3.
  
 5. SHT P3.1.1 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED.
 PLEASE USE THE SIGNATURE REQUIRED. FS 471.025.
  
 6. SHT P3.1.1 LATEST REVISION SUBMITTED IS REVISION
 #10. REVISION #10 WAS SUBMITTED PREVIOUSLY AND WAS
 SIGNED, SEALED & DATED ON 6-2-08. SHEET HAS BEEN DENIED
 BECAUSE NO NEW REVISION IS INDICATED. SECTION 106.1.3.
  
 7. SHT P5.1 A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME
 PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED.
 PLEASE USE THE SIGNATURE REQUIRED. FS 471.025.
  
 8. SHT P5.1 SHOWS A HOSE BIBB IN THE METER ROOM. NO
 FLOOR DRAIN IS INDICATED. PLEASE SHOW COMPLIANCE WITH
 SECTION 301.2 WHICH STATES THAT PLUMBING SHALL BE
 INSTALLED WITH DUE REGARD TO PRESERVATION OF THE
 STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE
 TO WALLS AND OTHER SURFACES THROUGH FIXTURE USEAGE.
  
 9. SHT P5.1 SHOWS THE 3" VTR BEING CHANGED TO AN AIR
 ADMITTANCE VALVE. SECTION 903.1 REQUIRES AT LEAST ONE
 VENT STACK THE SIZE OF WHICH IS NOT LESS THAN 1/2 OF
 THE REQUIRED SIZE OF THE BUILDING DRAIN TO RUN
 UNDIMINISHED IN SIZE AND DIRECTLY AS POSSIBLE FROM THE
 BUILDING DRAIN THROUGH TO THE OPEN AIR OR TO A VENT
 HEADER THAT EXTENDS TO THE OPEN AIR. PLEASE INDICATE
 HOW THIS WILL BE COMPLIED WITH.
  
 10. INFORMATIONAL. AS PREVIOUSLY REQUESTED, WHEN
 SUBMITTING REVISIONS, PLEASE TURN OFF ALL PREVIOUSLY
 CLOUDED REVISIONS ON THE FLOOR PLANS & RISERS AS WELL
 AS THE REVISION NUMBERS AS THIS CAUSES DELAYS IN THE
 PLAN REVIEW PROCESS. EACH CLOUD HAS TO BE SCRUTINIZED
 IN ORDER TO MAKE SURE ALL REVISIONS SUBMITTED HAVE BEEN
 REVIEWED. THE REVISION INDEX SHALL STILL SHOW ALL
 REVISION NUMBERS AND DATES. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS