2008-10-08 08:04:58 | REVISIONS DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT P2.31 A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| NAME PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED. |
| PLEASE USE THE SIGNATURE REQUIRED. FS 471.025. |
| |
| 2. SHT P2.31 SHOWS A HOSE BIBB IN THE METER ROOM. NO |
| FLOOR DRAIN IS INDICATED. PLEASE SHOW COMPLIANCE WITH |
| SECTION 301.2 WHICH STATES THAT PLUMBING SHALL BE |
| INSTALLED WITH DUE REGARD TO PRESERVATION OF THE |
| STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE |
| TO WALLS AND OTHER SURFACES THROUGH FIXTURE USEAGE. |
| |
| 3. SHT P2.31 SHOWS THE 3" VTR BEING CHANGED TO AN AIR |
| ADMITTANCE VALVE. SECTION 903.1 REQUIRES AT LEAST ONE |
| VENT STACK THE SIZE OF WHICH IS NOT LESS THAN 1/2 OF |
| THE REQUIRED SIZE OF THE BUILDING DRAIN TO RUN |
| UNDIMINISHED IN SIZE AND DIRECTLY AS POSSIBLE FROM THE |
| BUILDING DRAIN THROUGH TO THE OPEN AIR OR TO A VENT |
| HEADER THAT EXTENDS TO THE OPEN AIR. PLEASE INDICATE |
| HOW THIS WILL BE COMPLIED WITH. |
| |
| 4. SHT P2.31 INDICATES A REVISION #10 ON THE FLOOR |
| PLAN. REVISION #10 IS NOT INDICATED ON THE REVISION |
| INDEX IN THE TITLE BLOCK. PLEASE CORRELATE. SECTION |
| 106.1.3. |
| |
| 5. SHT P3.1.1 A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| NAME PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED. |
| PLEASE USE THE SIGNATURE REQUIRED. FS 471.025. |
| |
| 6. SHT P3.1.1 LATEST REVISION SUBMITTED IS REVISION |
| #10. REVISION #10 WAS SUBMITTED PREVIOUSLY AND WAS |
| SIGNED, SEALED & DATED ON 6-2-08. SHEET HAS BEEN DENIED |
| BECAUSE NO NEW REVISION IS INDICATED. SECTION 106.1.3. |
| |
| 7. SHT P5.1 A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME |
| PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED. |
| PLEASE USE THE SIGNATURE REQUIRED. FS 471.025. |
| |
| 8. SHT P5.1 SHOWS A HOSE BIBB IN THE METER ROOM. NO |
| FLOOR DRAIN IS INDICATED. PLEASE SHOW COMPLIANCE WITH |
| SECTION 301.2 WHICH STATES THAT PLUMBING SHALL BE |
| INSTALLED WITH DUE REGARD TO PRESERVATION OF THE |
| STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE |
| TO WALLS AND OTHER SURFACES THROUGH FIXTURE USEAGE. |
| |
| 9. SHT P5.1 SHOWS THE 3" VTR BEING CHANGED TO AN AIR |
| ADMITTANCE VALVE. SECTION 903.1 REQUIRES AT LEAST ONE |
| VENT STACK THE SIZE OF WHICH IS NOT LESS THAN 1/2 OF |
| THE REQUIRED SIZE OF THE BUILDING DRAIN TO RUN |
| UNDIMINISHED IN SIZE AND DIRECTLY AS POSSIBLE FROM THE |
| BUILDING DRAIN THROUGH TO THE OPEN AIR OR TO A VENT |
| HEADER THAT EXTENDS TO THE OPEN AIR. PLEASE INDICATE |
| HOW THIS WILL BE COMPLIED WITH. |
| |
| 10. INFORMATIONAL. AS PREVIOUSLY REQUESTED, WHEN |
| SUBMITTING REVISIONS, PLEASE TURN OFF ALL PREVIOUSLY |
| CLOUDED REVISIONS ON THE FLOOR PLANS & RISERS AS WELL |
| AS THE REVISION NUMBERS AS THIS CAUSES DELAYS IN THE |
| PLAN REVIEW PROCESS. EACH CLOUD HAS TO BE SCRUTINIZED |
| IN ORDER TO MAKE SURE ALL REVISIONS SUBMITTED HAVE BEEN |
| REVIEWED. THE REVISION INDEX SHALL STILL SHOW ALL |
| REVISION NUMBERS AND DATES. SECTION 106.1.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |