Plan Review Notes
Plan Review Notes For Permit 06110349
Permit Number 06110349
Review Stop E
Sequence Number 4
Notes
Date Text
2007-12-23 19:30:092007-12-23 19:30:09
  
 ** DENIED4TH REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE KNOW A COMPLETE REVIEW OF ENERGY
 CALCULATIONS CAN NOT BE DONE AT THIS TIME AS SHEETS
 E1.1A, AND E1.2 DOES NOT CORRELATE.
 PLEASE SEE FIXTURES ON E1.1A FOR PARKING LOT SHOW
 DOUBLE FIXTURES ON WEST SIDE HOWEVER THE FIXTURES ON
 WEST SIDE OF E1.2 ARE ALL SINGLE FIXTURES.
 PLEASE SEE E1.1A AS THE FIXTURES ON THE NORTH, EAST AND
 SOUTH SIDES WHICH ARE SHOWN ON E1.2 ARE MISSING? CAN
 NOT CONFIRM LIGHTING ON THE INPUT DATA REPORT. PLEASE
 SEE THE LIGHTING FOR INTERIOR LIGHTING NEEDS TO BE
 ADJUSTED TO MATCH WITH PLANS.
 PLEASE SEE THE AMOUNT OF INTERIOR 64 WATT FIXTURES IS
 NOT THE SAME IN THE IDR AS SHOWN ON PLANS. (MISSING
 SEPARATE ROOMS).
 ** PLEASE CLARIFY THE 150 500W FIXTURES. IS THIS AN
 ASSUMPTION FOR FUTURE LIGHTS?
 IF SO, HOW IS IT THAT NO ASSUMPTION WAS FIGURED FOR
 BUILDING #1 FOR FUTURE?
 THIS WAS NOTED ON PREVIOUS REVIEW AND RESPONSE ONLY
 STATES TO *SEE REVISED ENERGY CALCULATIONS*. PLEASE SEE
 THE SQ FT DOES NOT CORRELATE WITH ARCHITECTURAL PLANS
 AND PLEASE SEE THE OCCUPANCY SHALL BE STATED AS ON
 ARCHITECTURAL SHEETS FOR F-1. THIS IS NOT RETAIL AS
 SHOWN ON COVER SHEET OF ENERGY CALCULATIONS.
 13-415.2, 13-415.1.B.
 **PLEASE PROVIDE CORRECTED SHEETS FOR COORDINATION OF
 SITE AND UPDATE ENERGY CALCULATIONS.
 **PLEASE ALSO BE SURE WHEN RE-SUBMITTING PLANS THE
 OWNER AGENT IS SIGNED ON CERTIFICATION SHEET.
 13-101.1.1.1
 ** PLEASE KNOW AS THE FIXTURES FOR SITE ARE NOT
 CONFIRMED, CIRCUITING, LOADS AND PANEL SCHEDULES CAN
 NOT BE CONFIRMED AT THIS TIME.
  
  
 ** AS GONE OVER IN MEETING BEFORE PLANS WERE
 RESUBMITTED, PLEASE BE SURE ALL LIGHTING ON PLANS IS
 PLACED AND FIGURED INTO THE ENERGY CALCULATIONS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]