2007-12-23 19:30:09 | 2007-12-23 19:30:09 |
| |
| ** DENIED4TH REVIEW ** |
| |
| ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE KNOW A COMPLETE REVIEW OF ENERGY |
| CALCULATIONS CAN NOT BE DONE AT THIS TIME AS SHEETS |
| E1.1A, AND E1.2 DOES NOT CORRELATE. |
| PLEASE SEE FIXTURES ON E1.1A FOR PARKING LOT SHOW |
| DOUBLE FIXTURES ON WEST SIDE HOWEVER THE FIXTURES ON |
| WEST SIDE OF E1.2 ARE ALL SINGLE FIXTURES. |
| PLEASE SEE E1.1A AS THE FIXTURES ON THE NORTH, EAST AND |
| SOUTH SIDES WHICH ARE SHOWN ON E1.2 ARE MISSING? CAN |
| NOT CONFIRM LIGHTING ON THE INPUT DATA REPORT. PLEASE |
| SEE THE LIGHTING FOR INTERIOR LIGHTING NEEDS TO BE |
| ADJUSTED TO MATCH WITH PLANS. |
| PLEASE SEE THE AMOUNT OF INTERIOR 64 WATT FIXTURES IS |
| NOT THE SAME IN THE IDR AS SHOWN ON PLANS. (MISSING |
| SEPARATE ROOMS). |
| ** PLEASE CLARIFY THE 150 500W FIXTURES. IS THIS AN |
| ASSUMPTION FOR FUTURE LIGHTS? |
| IF SO, HOW IS IT THAT NO ASSUMPTION WAS FIGURED FOR |
| BUILDING #1 FOR FUTURE? |
| THIS WAS NOTED ON PREVIOUS REVIEW AND RESPONSE ONLY |
| STATES TO *SEE REVISED ENERGY CALCULATIONS*. PLEASE SEE |
| THE SQ FT DOES NOT CORRELATE WITH ARCHITECTURAL PLANS |
| AND PLEASE SEE THE OCCUPANCY SHALL BE STATED AS ON |
| ARCHITECTURAL SHEETS FOR F-1. THIS IS NOT RETAIL AS |
| SHOWN ON COVER SHEET OF ENERGY CALCULATIONS. |
| 13-415.2, 13-415.1.B. |
| **PLEASE PROVIDE CORRECTED SHEETS FOR COORDINATION OF |
| SITE AND UPDATE ENERGY CALCULATIONS. |
| **PLEASE ALSO BE SURE WHEN RE-SUBMITTING PLANS THE |
| OWNER AGENT IS SIGNED ON CERTIFICATION SHEET. |
| 13-101.1.1.1 |
| ** PLEASE KNOW AS THE FIXTURES FOR SITE ARE NOT |
| CONFIRMED, CIRCUITING, LOADS AND PANEL SCHEDULES CAN |
| NOT BE CONFIRMED AT THIS TIME. |
| |
| |
| ** AS GONE OVER IN MEETING BEFORE PLANS WERE |
| RESUBMITTED, PLEASE BE SURE ALL LIGHTING ON PLANS IS |
| PLACED AND FIGURED INTO THE ENERGY CALCULATIONS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |