2008-01-15 16:01:17 | BUILDING PLAN REVIEW |
| PERMIT: 06110349 |
| ADD: 5720 PREMIER PARK DR. BLDG# 3 |
| CONT:GLOBAL CONSTRUCTION ASSOCIATES LLC |
| TEL: (954)444-8463 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006 |
| REVISIONS |
| * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE |
| |
| 4THREVIEW- AS APERMIT APPLICATION! |
| ACTION: DENIED |
| |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. |
| A TRANSMITTAL LETTERLISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT BEFORE A PERMIT WILL BE ISSUED. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. |
| |
| 3) SEMI-COMPLIED, REQUIRES THREE "ORIGINAL"ORIGINAL |
| SIGNATURES NOT COPIES!!!! AND RAISED EMBOSSED SEALED |
| REPORTS. REPORTS SUPPLIED FROM JULY 17,2006 3RD |
| REQUEST, SUBMITTED (3) REPORTS DATED MAY 21, 2004, |
| STRUCTURAL SHEETS INDICATE A SOILS TEST WAS CONDUCTED |
| BY NUTTING ENGINEERING, PROJECT# 14157.1, JULY 17, |
| 2006. PLEASE PROVIDE 3 ORIGINAL DOCUMENTS SIGNED AND |
| SEALED. |
| FL BLD CODE 1804.2.2 QUESTIONABLE SOILS, WHERE THE |
| BEARINGCAPACITY IS NOT DEFINETLY KNOWN OR IS IN |
| QUESTION. WHERE THE BEARING CAPACITY OF THE SOIL IS NOT |
| DEFINITLY KNOWN OR IS IN QUESTION THE BUILDING OFFICIAL |
| MAY REQUIRE EXPLORATIONS, TEST OR OTHER ADEQUATE PROOF |
| AS TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDATIONS SUBMITTED |
| TO VERIFY BEARING CAPACITY SHALL BE CERTIFIED BY A |
| GEOTECHNICAL |
| REPORT FROM A DESIGN PROFESSIONAL PROPERLY LICENSED IN |
| THE STATE OF FLORIDA. |
| |
| |
| |
| |
| 4 -6 ) COMPLIED. |
| |
| 7)FOURTHREQUEST,FL BLD CODE 1609.1.4: |
| COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD |
| OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS |
| ,MISSING REPORTS ARE AS FOLLOWS: |
| A) STOREFRONT WINDOWS REPORTS SUPPLIED FROM YKKWILL |
| EITHER NEED ENGINERING CALCULATIONS OR THE DADE COUNTY |
| REPORT. THE STATE COVER SHEET INDICATES IF ANCHOR |
| CALCULATIONS HAVENOT BEEN VERIFIED BY A PE A 1/3RD |
| DECREASE NEEDS TO BE TAKEN. ALSO HIGHLIGHT AS TO WHICH |
| GLASS TYPE WILL BE INSTALLED IN THE FRAME FOR THE |
| POSITIVE AND NEGATIVE PRESSURES TO BE USED. |
| B) MULLIONS- UNDER STOREFRONT REPORT |
| C) SKYLIGHTS- THE SKYLIGHTS REPORTS ARE OK, PLANS NEED |
| WELDING INFO FOR THE SKYLIGHT BASE TO THE BARJOISTD) |
| EXTERIOR GLAZED DOORSREPORTS SUPPLIED FROM YKKWILL |
| EITHER NEED ENGINERING CALCULATIONS OR THE DADE COUNTY |
| REPORT. THE STATE COVER SHEET INDICATES IF ANCHOR |
| CALCULATIONS HAVENOT BEEN VERIFIED BY A PE A 1/3RD |
| DECREASE NEEDS TO BE TAKEN. ALSO HIGHLIGHT AS TO WHICH |
| GLASS TYPE WILL BE INSTALLED IN THE FRAME FOR THE |
| POSITIVE AND NEGATIVE PRESSURES TO BE USED. |
| E) EXTERIOR HOLLOW METAL DOORS-OK |
| F) ROLL UP DOORS-OK |
| G) LOUVERS- OK |
| H) ROOFING ASSEMBLIES- THE REPORT FROM FEDERAL |
| REFRENENCES THE WRONG NOA NUMBERAND THE AMOUNT OF PAGES |
| FOUND IN THE REPORT. |
| |
| 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| M) ABOVE GRADE SHALL MEET |
| THE PROVISIONS OF THE SMALL MISSILE TEST. |
| |
| 8-10) COMPLIED. |
| |
| 11) BUILDING PROVISO: SHOP DRAWINGS TO BE SUBMITTED FOR |
| ANCHORAGE OF EFIS MOLDINGS BEFORE START OF INSTALLATION |
| WITH FASTENING INFORMATION.1406.2.2 |
| |
| 12-15) COMPLIED. |
| |
| 16)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| BUILDING PLAN REVIEW |