2008-01-15 16:01:17BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES LLC
 TEL: (954)444-8463
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 4THREVIEW- AS APERMIT APPLICATION!
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE REMOVE & REPLACE ANY
 PAGES AS NECESSARY.
 A TRANSMITTAL LETTERLISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT BEFORE A PERMIT WILL BE ISSUED. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID.
  
 3) SEMI-COMPLIED, REQUIRES THREE "ORIGINAL"ORIGINAL
 SIGNATURES NOT COPIES!!!! AND RAISED EMBOSSED SEALED
 REPORTS. REPORTS SUPPLIED FROM JULY 17,2006 3RD
 REQUEST, SUBMITTED (3) REPORTS DATED MAY 21, 2004,
 STRUCTURAL SHEETS INDICATE A SOILS TEST WAS CONDUCTED
 BY NUTTING ENGINEERING, PROJECT# 14157.1, JULY 17,
 2006. PLEASE PROVIDE 3 ORIGINAL DOCUMENTS SIGNED AND
 SEALED.
 FL BLD CODE 1804.2.2 QUESTIONABLE SOILS, WHERE THE
 BEARINGCAPACITY IS NOT DEFINETLY KNOWN OR IS IN
 QUESTION. WHERE THE BEARING CAPACITY OF THE SOIL IS NOT
 DEFINITLY KNOWN OR IS IN QUESTION THE BUILDING OFFICIAL
 MAY REQUIRE EXPLORATIONS, TEST OR OTHER ADEQUATE PROOF
 AS TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDATIONS SUBMITTED
 TO VERIFY BEARING CAPACITY SHALL BE CERTIFIED BY A
 GEOTECHNICAL
 REPORT FROM A DESIGN PROFESSIONAL PROPERLY LICENSED IN
 THE STATE OF FLORIDA.
  
  
  
  
 4 -6 ) COMPLIED.
  
 7)FOURTHREQUEST,FL BLD CODE 1609.1.4:
 COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD
 OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS
 ,MISSING REPORTS ARE AS FOLLOWS:
 A) STOREFRONT WINDOWS REPORTS SUPPLIED FROM YKKWILL
 EITHER NEED ENGINERING CALCULATIONS OR THE DADE COUNTY
 REPORT. THE STATE COVER SHEET INDICATES IF ANCHOR
 CALCULATIONS HAVENOT BEEN VERIFIED BY A PE A 1/3RD
 DECREASE NEEDS TO BE TAKEN. ALSO HIGHLIGHT AS TO WHICH
 GLASS TYPE WILL BE INSTALLED IN THE FRAME FOR THE
 POSITIVE AND NEGATIVE PRESSURES TO BE USED.
 B) MULLIONS- UNDER STOREFRONT REPORT
 C) SKYLIGHTS- THE SKYLIGHTS REPORTS ARE OK, PLANS NEED
 WELDING INFO FOR THE SKYLIGHT BASE TO THE BARJOISTD)
 EXTERIOR GLAZED DOORSREPORTS SUPPLIED FROM YKKWILL
 EITHER NEED ENGINERING CALCULATIONS OR THE DADE COUNTY
 REPORT. THE STATE COVER SHEET INDICATES IF ANCHOR
 CALCULATIONS HAVENOT BEEN VERIFIED BY A PE A 1/3RD
 DECREASE NEEDS TO BE TAKEN. ALSO HIGHLIGHT AS TO WHICH
 GLASS TYPE WILL BE INSTALLED IN THE FRAME FOR THE
 POSITIVE AND NEGATIVE PRESSURES TO BE USED.
 E) EXTERIOR HOLLOW METAL DOORS-OK
 F) ROLL UP DOORS-OK
 G) LOUVERS- OK
 H) ROOFING ASSEMBLIES- THE REPORT FROM FEDERAL
 REFRENENCES THE WRONG NOA NUMBERAND THE AMOUNT OF PAGES
 FOUND IN THE REPORT.
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 8-10) COMPLIED.
  
 11) BUILDING PROVISO: SHOP DRAWINGS TO BE SUBMITTED FOR
 ANCHORAGE OF EFIS MOLDINGS BEFORE START OF INSTALLATION
 WITH FASTENING INFORMATION.1406.2.2
  
 12-15) COMPLIED.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]