Plan Review Notes
Plan Review Notes For Permit 06110349
Permit Number 06110349
Review Stop M
Sequence Number 3
Notes
Date Text
2007-10-12 16:43:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) N.O.A. SUBMITTED FOR THE LOUVERS IS MISSING THE
 ASSEMBLIES & SECTIONS (DRAWINGS), PLEASE SUBMIT THE
 COMPLETE N.O.A.
  
 2) THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING
 (REVIEW STAMPED) BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.WPB AMENDMENT
 TO FBC 106.3.3.
  
 3) NOT NOTICED AT LAST REVIEW ENERGY CALCULATIONS SHOW
 NO SKYLIGHTS, PLEASE CORRECT AS SKYLIGHTS ARE BEING
 INSTALLED.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  