2007-10-25 15:45:33 | ****DENIED***** |
| |
| |
| THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW |
| STILL NEED TO BE ADDRESSED: |
| |
| 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE |
| A LAYOUT OF THE FIRE SPRINKLER SYSTEM.THE PROJECT |
| SITE ADDRESS IN THE TITLE BLOCK OF THE SUBMITTED FIRE |
| SPRINKLER SHEETS IS INCORRECT.PLEASE BE ADVISED THAT |
| THE SUBMITTED SPRINKLER SHEETS WILL BE INCLUDED WITH |
| THE MASTER PERMIT SET OF PLANS; SPRINKLER SPEC SHEETS |
| NOT NEEDED AT THIS TIME, BUT SHALL BE REQUIRED WHEN THE |
| SPRINKLER CONTRACTOR APPLIES FOR THE SEPARATE PLANS AND |
| PERMIT. |
| |
| 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE |
| POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, |
| VESSELS, EQUIPMENT, ETC.COULD NOT LOCATE THIS COMMENT |
| AS PER YOUR RESPONSE |
| |
| 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| DEPARTMENT CONNECTIONS.COULD NOT LOCATE THIS COMMENT |
| AS PER YOUR RESPONSE |
| |
| 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.COULD |
| NOT LOCATE THIS COMMENT AS PER YOUR RESPONSE |
| |
| 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE |
| CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724 |
| FOR APPLICATIONS.COULD NOT LOCATE THIS COMMENT AS PER |
| YOUR RESPONSE |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLAN |
| EACH ITEM WAS ADDRESSED |
| |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |