Date |
Text |
2007-10-15 09:14:43 | 2007-10-15 09:14:43 |
| |
| **** DENIED 3RD REVIEW**** |
| |
| ** PLEASE KNOW THIS IS THE SECOND REVIEW UNDER PERMIT |
| APPLICATION AND THE THIRD REVIEW TOTAL. |
| ** PLEASE SEE THERE ARE STILL SEVERAL COMMENTS FROM THE |
| PREVIOUS TWO REVIEWS WHICH NEED TO BE ADDRESSED. |
| |
| |
| 1) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED |
| AND GAVE ALL CODES RELEVANT TO THE MINIMUM DESIGN TO BE |
| PLACED ON PLANS. NFPA-20 2003 IS RELEVANT TO PROJECT |
| AND WAS NOT PLACED ON PLANS WITH OTHER RELEVANT CODES. |
| PLEASE ADD TO SHEETS FOR ELECTRICAL AND FORWARD TO |
| ARCHITECT OF RECORD. |
| |
| 2) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WITH RESPECT |
| TO FBC CHAPTER 13. |
| PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO |
| NOT CORRELATE WITH PLANS. |
| PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE. |
| PLEASE SEE THE METHOD OF CONTROLS. |
| PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE. |
| *FOR EXAMPLE: SEE THE INPUT DATA REPORT WHICH HAS |
| 500WATT FIXTURES FOR INTERIOR FIXTURES, YET THE FIXTURE |
| LEGEND DOES NOT INDICATE ANY FIXTURES WITH THIS SAME |
| WATTAGE, IN FACT THE THERE ARE SEVERAL OTHER WATTAGES |
| NONE OF WHICH ARE ON THE INPUT DATA REPORT. |
| PLEASE SEE TYPE OF BUILDING NEEDS TO BE VERIFIED AS |
| THIS IS NOT RETAIL. |
| PLEASE SEE THE EXTERIOR LIGHTING DOES NOT CORRELATE |
| WITH PLANS AS THE INPUT DATA REPORT CONTAINS NO |
| FIXTURES FOR EXTERIOR LIGHTING. HOW IS THIS POSSIBLE |
| WHEN THE PLANS CONTAIN DOZENS OF FIXTURES??? PLEASE BE |
| SURE THE ADDRESS IS LISTED ON CALCULATIONS. PLEASE SEE |
| 13-415.1.B, 13-415.2 |
| |
| 3) NOTE: PLEASE SEE METHOD OF CONTROLS FOR LIGHTING IS |
| STILL NOT COMPLETE PER 13-415.1.ABC.1.1, .1.2. PLEASE |
| OVER RIDE SWITCH LOCATIONS ARE NOT SHOWN ON PLANS AS |
| REQUIRED FOR THE OCCUPANT ENTERING A SPACE AND BEING |
| ABLE TO SEE THE LIGHTING IN WHICH IS BEING OVER |
| RIDDEN. |
| PLEASE SEE THERE ARE STILL STANDARD DEVICES SHOWN ON |
| PLANS. |
| PLEASE SEE NO TIME SCHEDULING, AND NO MAXIMUM TIMES ON |
| OVER RIDES ARE SHOWN. |
| NO ZONES, NO LAYOUTS ETC |
| PLEASE SEE THE PREVIOUS TWO REVIEW NOTES BELOW: |
| |
| (REVIEW #2) |
| **PREVIOUS REVIEW NOTES** |
| PLEASE SEE FBC 2004 CHAPTER 13. THIS IS THE SAME |
| COMMENT AS PREVIOUS REVIEW. PLEASE SEE THE VERSION AS |
| SUBMITTED DOES NOT COMPLY WITH THE NEW CODE AS OF |
| DECEMBER 8TH, 2006. |
| PLEASE SEE AS THIS IS MENTIONED AS A SHELL BUILDING, |
| PLEASE SEE METHOD. |
| PLEASE SEE METHOD OF CONTROL STILL MENTIONS MANUAL |
| ON/OFF WHICH IS NOT POSSIBLE WHEN AUTOMATED MEANS IS |
| REQUIRED. |
| PLEASE SEE MISSING OVER RIDE CONTROLS AT THE POINT OF |
| ENTRANCE BY WAY OF CHOSEN DEVICES SO THE OCCUPANT CAN |
| SEE THE LIGHTING WHICH IS BEING CONTROLLED. IF OS TYPE |
| DEVICES ARE GOING TO BE INSTALLED FOR COVERAGE, PLEASE |
| SHOW LOCATIONS, TYPE OF DEVICES AND MAXIMUM TIMES ON |
| OVER RIDES |
| PLEASE SEE SEPARATE SPACES WHICH ONLY INDICATE STANDARD |
| SWITCHES. |
| PLEASE SEE INTERIOR LIGHTING WHICH DOES NOT SHOW ANY |
| AUTOMATED CONTROLS. |
| PLEASE SEE ZONING NOT SHOWN FOR LARGER SPACES. PLEASE |
| SEE ENERGY CALCULATIONS DO NOT INCLUDE ANY EXTERIOR |
| LIGHTING AS PLANS DO. |
| PLEASE BE SURE OWNER AGENT SIGNS ALL THREE COPIES. |
| PLEASE SEE THE ADDRESS SHALL BE SPECIFIC ON |
| CALCULATIONS. |
| PLEASE SEE PREVIOUS REVIEW NOTES BELOW. |
| PLEASE SEE FBC CHAPTER 13. |
| |
| (REVIEW #1) |
| ** PREVIOUS NOTES** |
| PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL" |
| FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE |
| ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR |
| EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| 13-415.1.AB.1, 13-415.2.ABC.1. |
| PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN |
| CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED |
| AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES. |
| PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING |
| HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL |
| BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE |
| DOES NOT REQUIRE ONE DESIGN OVER ANOTHER. |
| PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE |
| SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT |
| "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS |
| CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS |
| IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE |
| ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE |
| SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING |
| CONTROL PANEL. (700.12E). |
| |
| |
| 4) NOTE: PLEASE SEE THE LIGHTING LEVELS STILL DO NOT |
| COMPLY WITH THE MINIMUM LEVELS AS REQUIRED FOR |
| EXIT/EXIT DISCHARGE PER NFPA-101 7.8.1.3AND 7.9.2.2. |
| PLEASE SEE PHOTO-METRICS INDICATE FOR NORMAL OR |
| EMERGENCY FOR STAIRS LEADING TO THE PUBLIC RIGHT OF WAY |
| HOWEVER THE LEVELS UNDER NORMAL ARE NOT MEETING THE |
| MINIMUM OF 10FT CANDLES ON SEVERAL STAIRS. PLEASE ALSO |
| SEE THE DESIGNATION OF STAIR #5 NORMAL AND EMERGENCY IS |
| MISSING. |
| |
| 5) NOTE: AS REQUESTED ON THE TWO PREVIOUS REVIEWS, |
| PLEASE COMPLETE ALL INFORMATION ON PLANS FOR FIRE PUMP, |
| FIRE PUMP CONTROLLER ETC. |
| . |
| THE RESPONSE LETTER MENTIONS THIS WILL BE *DONE BY THE |
| FIRE SPRINKLER CONTRACTOR* |
| SOME CUT SHEETS WERE SUBMITTED HOWEVER NOT ALL. |
| AS STATED CLEARLY ON THE TWO PREVIOUS REVIEWS THIS |
| INFORMATION IS REQUIRED FOR *MINIMUM* CODE COMPLIANCE |
| FOR THE BASE BUILDING AND ALL INFORMATION SHALL BE |
| SUBMITTED UNDER THE BASE BUILDING PERMIT APPLICATION. |
| THIS IS IRRELEVANT OF THE SEPARATE PERMIT REQUIRED FOR |
| FIRE SPRINKLER AT A LATER DATE. |
| PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS. PLEASE |
| COMPLETE INFORMATION ON PLANS. |
| NEC 695, NFPA-20 CHAPTER 6, 7 ETC |
| CODES SECTIONS GIVEN BELOW FROM PREVIOUS REVIEWS REMAIN |
| THE SAME. |
| |
| **PREVIOUS REVIEW #2 NOTE: |
| AS NOTED ON PREVIOUS REVIEW. PLEASE COMPLETE ALL |
| INFORMATION ON PLANS AND PLEASE SUBMIT ALL SPECS/CUT |
| SHEETS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE |
| FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS REQUIRED |
| UNDER THE BASE BUILDING PLANS FOR REVIEW OF CODE |
| COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND |
| FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE |
| SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE |
| NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS |
| FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL |
| BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC |
| SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED. |
| PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10 |
| OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC. |
| PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY |
| CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE |
| INFORMATION WAS NOT SUBMITTED. |
| PLEASE SEE 110.3, AND 90.7. |
| PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA |
| 5 |
| |
| 6) NOTE:THIS NOTE FROM PREVIOUS REVIEW WILL REMAIN AS |
| INFORMATION ON FIRE PUMP IS NOT COMPLETE AND |
| VERIFICATION OF RISER CONDUCTORS ETC CAN NOT BE |
| REVIEWED UNTIL ALL INFORMATION IS ON PLANS AND |
| SUBMITTED. |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED ABOVE FOR |
| FEEDERS ETC. |
| 240.4, 310.16, 695, NFPA-20 CHAPTER 9 |
| |
| 7 NOTE:PLEASE SEE ACTUAL CALCULATIONS FOR LIGHT POLES |
| WILL BE REVIEWED BY STRUCTURAL REVIEWER. |
| ** NOTED FOR INFORMATION. |
| |
| 8) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH |
| RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. AS THIS |
| IS ONLY THE SECOND REVIEW UNDER PERMIT APPLICATION AS |
| THE INITIAL REVIEW WAS UNDER *PLAN REVIEW*. |
| PLEASE ADDRESS ALL COMMENTS. |
| |
| 9) NOTE: PLEASE SEE ALL LANDSCAPE PLANS AS SUBMITTED |
| ARE NOT SIGNED DATED OR SEALED BY THE RESPONSIBLE |
| DESIGNER(S) OF RECORD. |
| SEE ONLY SHEET 1 OF 6 WAS SIGNED, AND SEALED. |
| FS 481.221 |
| |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| PLANS. |
| |
| ** IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-10-15 07:47:17 | 2007-10-15 07:47:17 |
| |
| IN REVIEW |
2007-10-14 16:02:30 | 2007-10-14 16:02:30 |
| REVIEW WILL CONTINUE ON 10/15, NOTES WILL FOLLOW ONCE |
| COMPLETED. |
| REVIEW WILL BE GOING INTO A *F* STATUS. |