Plan Review Notes
Plan Review Notes For Permit 06110349
Permit Number 06110349
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-15 09:14:432007-10-15 09:14:43
  
 **** DENIED 3RD REVIEW****
  
 ** PLEASE KNOW THIS IS THE SECOND REVIEW UNDER PERMIT
 APPLICATION AND THE THIRD REVIEW TOTAL.
 ** PLEASE SEE THERE ARE STILL SEVERAL COMMENTS FROM THE
 PREVIOUS TWO REVIEWS WHICH NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 AND GAVE ALL CODES RELEVANT TO THE MINIMUM DESIGN TO BE
 PLACED ON PLANS. NFPA-20 2003 IS RELEVANT TO PROJECT
 AND WAS NOT PLACED ON PLANS WITH OTHER RELEVANT CODES.
 PLEASE ADD TO SHEETS FOR ELECTRICAL AND FORWARD TO
 ARCHITECT OF RECORD.
  
 2) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WITH RESPECT
 TO FBC CHAPTER 13.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO
 NOT CORRELATE WITH PLANS.
 PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE.
 PLEASE SEE THE METHOD OF CONTROLS.
 PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE.
 *FOR EXAMPLE: SEE THE INPUT DATA REPORT WHICH HAS
 500WATT FIXTURES FOR INTERIOR FIXTURES, YET THE FIXTURE
 LEGEND DOES NOT INDICATE ANY FIXTURES WITH THIS SAME
 WATTAGE, IN FACT THE THERE ARE SEVERAL OTHER WATTAGES
 NONE OF WHICH ARE ON THE INPUT DATA REPORT.
 PLEASE SEE TYPE OF BUILDING NEEDS TO BE VERIFIED AS
 THIS IS NOT RETAIL.
 PLEASE SEE THE EXTERIOR LIGHTING DOES NOT CORRELATE
 WITH PLANS AS THE INPUT DATA REPORT CONTAINS NO
 FIXTURES FOR EXTERIOR LIGHTING. HOW IS THIS POSSIBLE
 WHEN THE PLANS CONTAIN DOZENS OF FIXTURES??? PLEASE BE
 SURE THE ADDRESS IS LISTED ON CALCULATIONS. PLEASE SEE
 13-415.1.B, 13-415.2
  
 3) NOTE: PLEASE SEE METHOD OF CONTROLS FOR LIGHTING IS
 STILL NOT COMPLETE PER 13-415.1.ABC.1.1, .1.2. PLEASE
 OVER RIDE SWITCH LOCATIONS ARE NOT SHOWN ON PLANS AS
 REQUIRED FOR THE OCCUPANT ENTERING A SPACE AND BEING
 ABLE TO SEE THE LIGHTING IN WHICH IS BEING OVER
 RIDDEN.
 PLEASE SEE THERE ARE STILL STANDARD DEVICES SHOWN ON
 PLANS.
 PLEASE SEE NO TIME SCHEDULING, AND NO MAXIMUM TIMES ON
 OVER RIDES ARE SHOWN.
 NO ZONES, NO LAYOUTS ETC
 PLEASE SEE THE PREVIOUS TWO REVIEW NOTES BELOW:
  
 (REVIEW #2)
 **PREVIOUS REVIEW NOTES**
 PLEASE SEE FBC 2004 CHAPTER 13. THIS IS THE SAME
 COMMENT AS PREVIOUS REVIEW. PLEASE SEE THE VERSION AS
 SUBMITTED DOES NOT COMPLY WITH THE NEW CODE AS OF
 DECEMBER 8TH, 2006.
 PLEASE SEE AS THIS IS MENTIONED AS A SHELL BUILDING,
 PLEASE SEE METHOD.
 PLEASE SEE METHOD OF CONTROL STILL MENTIONS MANUAL
 ON/OFF WHICH IS NOT POSSIBLE WHEN AUTOMATED MEANS IS
 REQUIRED.
 PLEASE SEE MISSING OVER RIDE CONTROLS AT THE POINT OF
 ENTRANCE BY WAY OF CHOSEN DEVICES SO THE OCCUPANT CAN
 SEE THE LIGHTING WHICH IS BEING CONTROLLED. IF OS TYPE
 DEVICES ARE GOING TO BE INSTALLED FOR COVERAGE, PLEASE
 SHOW LOCATIONS, TYPE OF DEVICES AND MAXIMUM TIMES ON
 OVER RIDES
 PLEASE SEE SEPARATE SPACES WHICH ONLY INDICATE STANDARD
 SWITCHES.
 PLEASE SEE INTERIOR LIGHTING WHICH DOES NOT SHOW ANY
 AUTOMATED CONTROLS.
 PLEASE SEE ZONING NOT SHOWN FOR LARGER SPACES. PLEASE
 SEE ENERGY CALCULATIONS DO NOT INCLUDE ANY EXTERIOR
 LIGHTING AS PLANS DO.
 PLEASE BE SURE OWNER AGENT SIGNS ALL THREE COPIES.
 PLEASE SEE THE ADDRESS SHALL BE SPECIFIC ON
 CALCULATIONS.
 PLEASE SEE PREVIOUS REVIEW NOTES BELOW.
 PLEASE SEE FBC CHAPTER 13.
  
 (REVIEW #1)
 ** PREVIOUS NOTES**
 PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL"
 FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE
 ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR
 EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1, 13-415.2.ABC.1.
 PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN
 CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED
 AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES.
 PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL
 BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE
 DOES NOT REQUIRE ONE DESIGN OVER ANOTHER.
 PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE
 SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT
 "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS
 CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS
 IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE
 ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING
 CONTROL PANEL. (700.12E).
  
  
 4) NOTE: PLEASE SEE THE LIGHTING LEVELS STILL DO NOT
 COMPLY WITH THE MINIMUM LEVELS AS REQUIRED FOR
 EXIT/EXIT DISCHARGE PER NFPA-101 7.8.1.3AND 7.9.2.2.
 PLEASE SEE PHOTO-METRICS INDICATE FOR NORMAL OR
 EMERGENCY FOR STAIRS LEADING TO THE PUBLIC RIGHT OF WAY
 HOWEVER THE LEVELS UNDER NORMAL ARE NOT MEETING THE
 MINIMUM OF 10FT CANDLES ON SEVERAL STAIRS. PLEASE ALSO
 SEE THE DESIGNATION OF STAIR #5 NORMAL AND EMERGENCY IS
 MISSING.
  
 5) NOTE: AS REQUESTED ON THE TWO PREVIOUS REVIEWS,
 PLEASE COMPLETE ALL INFORMATION ON PLANS FOR FIRE PUMP,
 FIRE PUMP CONTROLLER ETC.
 .
 THE RESPONSE LETTER MENTIONS THIS WILL BE *DONE BY THE
 FIRE SPRINKLER CONTRACTOR*
 SOME CUT SHEETS WERE SUBMITTED HOWEVER NOT ALL.
 AS STATED CLEARLY ON THE TWO PREVIOUS REVIEWS THIS
 INFORMATION IS REQUIRED FOR *MINIMUM* CODE COMPLIANCE
 FOR THE BASE BUILDING AND ALL INFORMATION SHALL BE
 SUBMITTED UNDER THE BASE BUILDING PERMIT APPLICATION.
 THIS IS IRRELEVANT OF THE SEPARATE PERMIT REQUIRED FOR
 FIRE SPRINKLER AT A LATER DATE.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS. PLEASE
 COMPLETE INFORMATION ON PLANS.
 NEC 695, NFPA-20 CHAPTER 6, 7 ETC
 CODES SECTIONS GIVEN BELOW FROM PREVIOUS REVIEWS REMAIN
 THE SAME.
  
 **PREVIOUS REVIEW #2 NOTE:
 AS NOTED ON PREVIOUS REVIEW. PLEASE COMPLETE ALL
 INFORMATION ON PLANS AND PLEASE SUBMIT ALL SPECS/CUT
 SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE
 FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS REQUIRED
 UNDER THE BASE BUILDING PLANS FOR REVIEW OF CODE
 COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND
 FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE
 SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE
 NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS
 FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL
 BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC
 SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED.
 PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10
 OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC.
 PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY
 CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE
 INFORMATION WAS NOT SUBMITTED.
 PLEASE SEE 110.3, AND 90.7.
 PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA
 5
  
 6) NOTE:THIS NOTE FROM PREVIOUS REVIEW WILL REMAIN AS
 INFORMATION ON FIRE PUMP IS NOT COMPLETE AND
 VERIFICATION OF RISER CONDUCTORS ETC CAN NOT BE
 REVIEWED UNTIL ALL INFORMATION IS ON PLANS AND
 SUBMITTED.
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED ABOVE FOR
 FEEDERS ETC.
 240.4, 310.16, 695, NFPA-20 CHAPTER 9
  
 7 NOTE:PLEASE SEE ACTUAL CALCULATIONS FOR LIGHT POLES
 WILL BE REVIEWED BY STRUCTURAL REVIEWER.
 ** NOTED FOR INFORMATION.
  
 8) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. AS THIS
 IS ONLY THE SECOND REVIEW UNDER PERMIT APPLICATION AS
 THE INITIAL REVIEW WAS UNDER *PLAN REVIEW*.
 PLEASE ADDRESS ALL COMMENTS.
  
 9) NOTE: PLEASE SEE ALL LANDSCAPE PLANS AS SUBMITTED
 ARE NOT SIGNED DATED OR SEALED BY THE RESPONSIBLE
 DESIGNER(S) OF RECORD.
 SEE ONLY SHEET 1 OF 6 WAS SIGNED, AND SEALED.
 FS 481.221
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-15 07:47:172007-10-15 07:47:17
  
 IN REVIEW
2007-10-14 16:02:302007-10-14 16:02:30
 REVIEW WILL CONTINUE ON 10/15, NOTES WILL FOLLOW ONCE
 COMPLETED.
 REVIEW WILL BE GOING INTO A *F* STATUS.