Date |
Text |
2007-11-01 10:11:10 | BUILDING PLAN REVIEW |
| PERMIT: 06110349 |
| ADD: 5720 PREMIER PARK DR. BLDG# 3 |
| CONT:GLOBAL CONSTRUCTION ASSOCIATES LLC |
| TEL: (954)444-8463 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006 |
| REVISIONS |
| * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE |
| |
| 3RDREVIEW- AS APERMIT APPLICATION! |
| ACTION: DENIED |
| |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. |
| A TRANSMITTAL LETTERLISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT BEFORE A PERMIT WILL BE ISSUED. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. |
| |
| 3) SEMI-COMPLIED, REQUIRES THREE ORIGINAL SIGNED AND |
| SEALED REPORTS FROM JULY 17,2006 3RD REQUEST, SUBMITTED |
| (3) REPORTS DATED MAY 21, 2004, STRUCTURAL SHEETS |
| INDICATE A SOILS TEST WAS CONDUCTED BY NUTTING |
| ENGINEERING, PROJECT# 14157.1, JULY 17, 2006. PLEASE |
| PROVIDE 3 ORIGINAL DOCUMENTS SIGNED AND SEALED. |
| FL BLD CODE 1804.2.2 QUESTIONABLE SOILS, WHERE THE |
| BEARINGCAPACITY IS NOT DEFINETLY KNOWN OR IS IN |
| QUESTION. WHERE THE BEARING CAPACITY OF THE SOIL IS NOT |
| DEFINITLY KNOWN OR IS IN QUESTION THE BUILDING OFFICIAL |
| MAY REQUIRE EXPLORATIONS, TEST OR OTHER ADEQUATE PROOF |
| AS TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDATIONS SUBMITTED |
| TO VERIFY BEARING CAPACITY SHALL BE CERTIFIED BY A |
| GEOTECHNICAL |
| REPORT FROM A DESIGN PROFESSIONAL PROPERLY LICENSED IN |
| THE STATE OF FLORIDA. |
| |
| |
| |
| |
| 4 A) FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| ONE OR MORE OF THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQ FT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| OR METHODS OF CONSTRUCTION |
| |
| 4B) SECOND REQUEST, SINCE THIS BUILDING WILL REQUIRE A |
| RESIDENT INSPECTORSUBMITTALS(3) SETS OF PLANS, |
| REPORTS, AND OR OTHER REQUIRED SUBMITTALS (PRODUCT |
| APPROVALS) WILL BE REQUIRED FOR REVIEW. |
| 1) MISSING (1)SOILS REPORT LISTED ABOVE. |
| 2) LIGHTING POLES- ONLY 2 REPORT SUBMITTED, RAISED SEAL |
| ILLEGIBLE, NOT EMBOSSED ENOUGH TO READ, MISSING THE |
| PRINTED NAME OF ENGINEER IN TITLE BLOCK 61G15-23.002(2) |
| FL. ADMIN. CODE. PLANS SIGNED & SEALED BY A |
| PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: NAME, |
| ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, THE NAME |
| AND LICENSE NUMBER OF THE ENGINEER AND THE NAME, |
| ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER IS |
| PRACTICING (471.025 F.S. AND 471.023 F.S.). |
| |
| 5-6 ) COMPLIED. |
| |
| 7)THIRD REQUEST,FL BLD CODE 1609.1.4: COMPONENTS |
| & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS |
| ARE AS FOLLOWS: |
| A) STOREFRONT WINDOWS |
| B) MULLIONS |
| C) SKYLIGHTS |
| D) EXTERIOR GLAZED DOORS |
| E) EXTERIOR HOLLOW METAL DOORS |
| F) ROLL UP DOORS |
| G) LOUVERS |
| H) ROOFING ASSEMBLIES |
| |
| 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| M) ABOVE GRADE SHALL MEET |
| THE PROVISIONS OF THE SMALL MISSILE TEST. |
| |
| 8)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| WWW.FLORIDABUILDING.ORG |
| |
| 9)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 10) THIS SUBMITTAL DOESN'T INCORPORATE ANY ROOFING |
| PRODUCT APPROVALS, HERE IS A LIST OF COMMON ISSUES THAT |
| WILL FAIL A ROOFING REPORT SUBMITTAL:THIS ROOF IS |
| MISSING OR NOT INCOMPLIANCE WITH THE FOLLOW |
| ITEMS: |
| ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___ |
| CONTRACTOR FAILED TO INDICATE WHICH SYSTEM OR SUBSYSTEM |
| WILL BE USED. |
| ___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| ___ . |
| ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| THE FASTENERRESISTANCE BE LESS THAN THATREQUIRED, |
| AS DETERMINED BY THE BUILDING OFFICIAL, A REVISED |
| FASTENER SPACING, PREPAREDSIGNEDAND SEALED BY A |
| FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| SUBMITTED. |
| ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| ENHANCED FASTENING ALLOWED. |
| |
| 11) BUILDING PROVISO: SHOP DRAWINGS TO BE SUBMITTED FOR |
| ANCHORAGE OF EFIS MOLDINGS BEFORE START OF INSTALLATION |
| WITH FASTENING INFORMATION.1406.2.2 |
| |
| 12) COMPLIED. |
| |
| 13) COMPLIED. |
| |
| 14)COMPLIED. |
| |
| 15) THIRD REQUEST, NOTE WITH THE PRODUCT APPROVALS NOT |
| SUBMITTED THE ROLL UP DOORS MAY OR MAY NOT REQUIRE DOOR |
| BUCKS AND ATTACHMENT.1714.5.4.2. |
| |
| 16)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |