2007-06-18 17:37:58 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK - SHELL INDICATED ON APPLICATION. |
| |
| 2. SHT A-5 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| SUBSECTIONS & TABLES. IN THE CALCULATIONS SHOW 1/2 AREA |
| OF ALL VERTICAL WALLS INCLUDING PARAPETS. THESE |
| CALCULATIONS ARE REQUIRED FOR THE LOWER ROOFS ALSO. |
| INDICATE THE ELEVATIONS FOR THE ROOF, HIGH END AND LOW |
| END, TO VERIFY PARAPET WALL CONTRIBUTION. |
| ****NO RESPONSE/NOT ADDRESSED. |
| |
| 3. SHTS A-5 & P3.3.1. WITH THE SLOPE OF THE ROOF AS |
| INDICATED ON SHT A-5, EXPLAIN HOW ALL ROOF DRAINS SHOW |
| THE SAME SQUARE FOOTAGE, (18930SF), DRAINING THROUGH |
| EACH DRAIN. ALSO THE ROOF DRAINS ON THE END AREAS OF |
| THE BUILDING HAVE EXTRA PARAPET WALL SQUARE FOOTAGE |
| THAT DOES NOT CONTRIBUTE TO THE INTERNAL SECTIONS OF |
| THE ROOF. |
| ****NO RESPONSE/NOT ADDRESSED. |
| |
| 4. SHT A-8 DETAILS 1/A-8 & 3/A-8 BOTH SCALE OUT TO |
| APPROXAMATELY 2'9" FROM THE ROOF TO THE TOP OF THE |
| PARAPET. PLEASE CLARIFY AS THE ROOF PLAN INDICATES |
| 1/4"/FT SLOPE @ 150' AND THE PARAPET ON THE LOW END |
| SHOULD BE APPROXAMATLY 4' HIGHER WITH BOTH PARAPETS |
| BEING 33'-0" AFF. |
| ****NO RESPONSE/NOT ADDRESSED. |
| |
| 5. SUBMIT STORM RISER DIAGRAMS SHOWING ALL PIPE SIZES & |
| OFFSETS. SECTION 106.3.5.1.3.ARE THE RISER DIAGRAMS |
| TO BE PIPED TO THE CATCH BASINS INDIVIDUALLY, OR TO BE |
| TIED TOGETHER PRIOR TO THE CATCH BASINS? IF TIED |
| TOGETHER, SIZING SHALL BE PER TABLE 1106.3. |
| ****NO RESPONSE/NOT ADDRESSED. |
| |
| 6. NO INDICATION OF VENTING IS SHOWN. PLEASE INDICATE |
| IF VENTS RUN THRU THE ROOF WILL BE INSTALLED UNDER THE |
| SHELL PERMIT, OR WITH THE TENANT BUILDOUT |
| PERMIT/PERMITS. SECTION 106.1.1. |
| ****NO RESPONSE/NOT ADDRESSED. |
| |
| 7. SHT P5.1 AN RPZV BACKFLOW IS REQUIRED ON THE WATER |
| SERVICE OF THE BUILDING. SECTION 608.13.2. PLEASE |
| INDICATE ON THE WATER RISER DIAGRAM OR THE PLUMBING |
| FLOOR PLAN. |
| ****NO RESPONSE/NOT ADDRESSED. |
| |
| REVIEW BY KEN STEVENS |