Plan Review Notes
Plan Review Notes For Permit 06110349
Permit Number 06110349
Review Stop M
Sequence Number 2
Notes
Date Text
2007-07-24 09:11:26*** FOR PERMIT ***
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO SHOW ALL ASSUMED A/C
 SYSTEMS FOR FUTURE INSTALLATION 2004 FBC 13-101.1.6
 SHELL BUILDINGS.
 NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS FOR FUTURE
 INSTALLATION, SEE 2004 FBC/M 13-407.1.ABC.1.
  
 3) AS REQUESTED IN LAST REVIEW, PLEASE SUBMIT STATE
 PRODUCT APPROVALS OR NOTICE OF ACCEPTANCE FOR LOUVERS
 TO BE INSTALLED (NOT JUST MANUFACTURER'S
 SPECIFICATION'S).
  
 4) SEE BUILDING REVIEW NOTES 8 AND 9, ALSO ELECTRICAL
 REVIEW NOTE 1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.