2007-07-24 09:11:26 | *** FOR PERMIT *** |
| *** DENIED *** |
| 1) ENERGY CALCULATIONS NEED TO SHOW ALL ASSUMED A/C |
| SYSTEMS FOR FUTURE INSTALLATION 2004 FBC 13-101.1.6 |
| SHELL BUILDINGS. |
| NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO |
| DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS |
| AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY |
| WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE |
| CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL |
| ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL |
| LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE |
| LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO |
| THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS |
| COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL |
| CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S) |
| USING METHODS A, B OR C SHALL BE SUBMITTED WHEN |
| COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS |
| PERMITTED. |
| |
| 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS FOR FUTURE |
| INSTALLATION, SEE 2004 FBC/M 13-407.1.ABC.1. |
| |
| 3) AS REQUESTED IN LAST REVIEW, PLEASE SUBMIT STATE |
| PRODUCT APPROVALS OR NOTICE OF ACCEPTANCE FOR LOUVERS |
| TO BE INSTALLED (NOT JUST MANUFACTURER'S |
| SPECIFICATION'S). |
| |
| 4) SEE BUILDING REVIEW NOTES 8 AND 9, ALSO ELECTRICAL |
| REVIEW NOTE 1, PLEASE CORRECT. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |