2007-07-11 12:07:10 | ****DENIED***** |
| |
| |
| THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW |
| STILL NEED TO BE ADDRESSED: |
| |
| |
| 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION SHALL COMPLY WITH NFPA241. |
| |
| 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| PROPERTY OR VICINITY THEREOF. |
| |
| 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE |
| A LAYOUT OF THE FIRE SPRINKLER SYSTEM. |
| |
| 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE |
| POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, |
| VESSELS, EQUIPMENT, ETC. |
| |
| 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| DEPARTMENT CONNECTIONS. |
| |
| 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY. |
| |
| 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE |
| CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724 |
| FOR APPLICATIONS. |
| |
| 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| 80. |
| |
| 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND |
| EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B". |
| |
| 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC. |
| |
| 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED |
| FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| |
| 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. |
| |
| 19.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY |
| ADDRESSABLE. |
| |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLAN |
| EACH ITEM WAS ADDRESSED |
| |
| |
| |