2007-07-11 12:07:10****DENIED*****
  
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW
 STILL NEED TO BE ADDRESSED:
  
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA241.
  
 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE
 A LAYOUT OF THE FIRE SPRINKLER SYSTEM.
  
 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.
  
 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
  
 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE
 CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724
 FOR APPLICATIONS.
  
 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC.
  
 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 19.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLAN
 EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW