2007-06-10 10:32:03**** UNSAT 2ND REVIEW****
  
 ** PLANS NOW SUBMITTED FOR PERMIT. THIS IS THE FIRST
 REVIEW UNDER PERMIT.
 PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 UNDER *PLAN REVIEW* WHICH STILL NEED TO BE ADDRESSED
 ALONG WITH SOME NEW COMMENTS.
 ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED IN
 DESIGN OR INFORMATION PROVIDED FOR CODE COMPLIANCE
 REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT YET BE MADE.
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED CONTAIN STAMPS
 FROM ANOTHER BUILDING DEPARTMENT AND MUNICIPALITY WHICH
 IS NOT PERMITTED. PLEASE KNOW ALL NEW SHEETS WILL BE
 REQUIRED TO BE SUBMITTED.
 PLEASE SEE SOME SHEETS EVEN CONTAIN SIGN OFFS FROM THAT
 SAME JURISDICTION ALTHOUGH PLANS INDICATE WORK IN THE
 CITY OF WEST PALM BEACH?
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW AS STATED
 REQUESTS FOR ALL OLD/VOIDED SHEETS TO BE COMPLETELY
 REMOVED FROM SETS AND ONLY TO INSERT NEW REVISED SHEETS
 INTO THE COMPLETED SETS FOR REVIEW AND STAMPING. PLEASE
 SEE SETS STILL CONTAIN OLD SHEETS, PLEASE REMOVE.
 PLEASE SEE COMMENT ABOVE FOR NEW SHEETS NEEDED.
  
 3) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS FOR
 *INITIALS* BEING USED IN LIEU OF ARCHITECT SIGNATURE.
 PLEASE SEE FS 481.221.
 A LETTER FOR SIGNATURE VERIFICATION WILL BE REQUIRED.
 THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS TIME
 FOR INFORMATIONAL PURPOSE. OTHER SHEETS ARE SIGNED.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES FOR CODE TO BE
 STATED ON PLANS. PLEASE SEE MOST WERE DONE, HOWEVER
 PLEASE SEE THE FOLLOWING.
 2004 FBC W/2006 REVISIONS.
 2003 NFPA-20
  
 5) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. THIS IS THE
 SAME COMMENT AS PREVIOUS REVIEW. PLEASE SEE THE VERSION
 AS SUBMITTED DOES NOT COMPLY WITH THE NEW CODE AS OF
 DECEMBER 8TH, 2006.
 PLEASE SEE AS THIS IS MENTIONED AS A SHELL BUILDING,
 PLEASE SEE METHOD.
 PLEASE SEE METHOD OF CONTROL STILL MENTIONS MANUAL
 ON/OFF WHICH IS NOT POSSIBLE WHEN AUTOMATED MEANS IS
 REQUIRED.
 PLEASE SEE MISSING OVER RIDE CONTROLS AT THE POINT OF
 ENTRANCE BY WAY OF CHOSEN DEVICES SO THE OCCUPANT CAN
 SEE THE LIGHTING WHICH IS BEING CONTROLLED. IF OS TYPE
 DEVICES ARE GOING TO BE INSTALLED FOR COVERAGE, PLEASE
 SHOW LOCATIONS, TYPE OF DEVICES AND MAXIMUM TIMES ON
 OVER RIDES
 PLEASE SEE SEPARATE SPACES WHICH ONLY INDICATE STANDARD
 SWITCHES.
 PLEASE SEE INTERIOR LIGHTING WHICH DOES NOT SHOW ANY
 AUTOMATED CONTROLS.
 PLEASE SEE ZONING NOT SHOWN FOR LARGER SPACES. PLEASE
 SEE ENERGY CALCULATIONS DO NOT INCLUDE ANY EXTERIOR
 LIGHTING AS PLANS DO.
 PLEASE BE SURE OWNER AGENT SIGNS ALL THREE COPIES.
 PLEASE SEE THE ADDRESS SHALL BE SPECIFIC ON
 CALCULATIONS.
 PLEASE SEE PREVIOUS REVIEW NOTES BELOW.
 PLEASE SEE FBC CHAPTER 13.
 ** PREVIOUS NOTES**
 PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL"
 FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE
 ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR
 EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1, 13-415.2.ABC.1.
 PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN
 CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED
 AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES.
 PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL
 BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE
 DOES NOT REQUIRE ONE DESIGN OVER ANOTHER.
 PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE
 SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT
 "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS
 CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS
 IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE
 ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING
 CONTROL PANEL. (700.12E).
  
  
 6) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9. PLEASE SEE NO
 PHOTO-METRICS INDICATE FOR NORMAL OR EMERGENCY FOR
 STAIRS LEADING TO THE PUBLIC RIGHT OF WAY.
 PLEASE SEE PHOTO-METRICS SHOULD INDICATE LEVELS UNDER
 NORMAL/EMERGENCY ON FLAT EGRESS PATHS (SAME FOR BOTH
 CONDITIONS).
 ** NOTES FROM PREVIOUS REVIEW**
 PLEASE SEE THAT MINIMUM BATTERY BACK UP LIGHTS OF SOME
 KIND WILL BE REQUIRED FOR EGRESS AREAS WHICH INCLUDE
 EXTERIOR STAIRS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 MINIMUM FOOT CANDLES UNDER NORMAL POWER AND MINIMUM
 FOOT CANDLES REQUIRED UNDER EMERGENCY POWER. 7.8.1.3,
 7.9.2.2. PLEASE KNOW THESE LIGHTING LEVELS SHOWN ON
 PHOTO-METRICS WILL BE REQUIRED ON ELECTRICAL PLANS FOR
 REVIEW WHETHER OR NOT THESE COMMENTS ARE MADE BY FIRE
 REVIEW.
  
 7) NOTE:AS NOTED ON PREVIOUS REVIEW, NOT ALL REQUIRED
 SIGNAGE OR NOTES IS ON PLANS.
 ** PREVIOUS REVIEW NOTES** PLEASE SEE 230.2E WHICH
 SPEAKS OF SIGNAGE REQUIRED FOR ALL SERVICE FEEDING ONE
 BUILDING. PLEASE SEE THAT RISER ONLY INDICATES 2-MAINS
 FOR THIS BUILDING, WHEN IN FACT THE MAIN FOR THE FIRE
 PUMP SHOULD ALSO BE NOTED AND LABELED. PLEASE ALSO
 PLACE NOTES ON RISER FOR SIGNAGE WHICH WILL BE REQUIRED
 FOR ALL MAINS AND SERVICE LOCATIONS. PLEASE SEE AS THE
 JOCKEY PUMP IS BEING FED FROM THE NORMAL HOUSE PANEL,
 THIS SHALL ALSO BE LABELED ACCORDINGLY. 695.4(B)3
  
 8) NOTE:AS NOTED ON PREVIOUS REVIEW. NO INFORMATION
 WAS SUBMITTED OR CHANGED ON PLANS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE
 FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS REQUIRED
 UNDER THE BASE BUILDING PLANS FOR REVIEW OF CODE
 COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND
 FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE
 SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE
 NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS
 FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL
 BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC
 SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED.
 PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10
 OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC.
 PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY
 CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE
 INFORMATION WAS NOT SUBMITTED.
 PLEASE SEE 110.3, AND 90.7.
 PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA
 5
  
 9) NOTE:THIS NOTE FROM PREVIOUS REVIEW WILL REMAIN AS
 INFORMATION ON FIRE PUMP IS NOT COMPLETE AND
 VERIFICATION OF RISER CONDUCTORS ETC CAN NOT BE
 REVIEWED.
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED ABOVE FOR
 FEEDERS ETC.
 240.4, 310.16, 695, NFPA-20 CHAPTER 9
  
 10) NOTE:SAME NOTE AS PREVIOUS REVIEW. NO INFORMATION
 SUBMITTED. AS THE POLES ON SITE ARE ALREADY BEING
 INSTALLED FOR OTHER BUILDINGS THIS INFORMATION SHOULD
 BE READILY AVAILABLE.
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT OR INDICATE REQUIREMENTS FOR WIND LOAD
 CALCULATIONS FOR BUILDING REVIEW FOR FBC 2004 140MPH.
  
 11) NOTE: PLEASE CLARIFY WHY LEVELS FOR STROBES ON
 SCHEDULE ARE STILL BEING SHOWN AT 15CD?
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER 11, MORE SPECIFICALLY
 11-4.28, .1.2, AND .3(4). PLEASE ALSO SEE NFPA-72
 2002.
 THIS MAY OR MAY NOT CHANGE ACTUAL SHOWN UNITS. AS FOR
 MINIMUM CANDELA LEVELS SEE ABOVE AS NOTED.
  
  
 12) NOTE: PLEASE SEE THE RESPONSE LETTER AS SUBMITTED
 DOES NOT RESPOND TO ALL COMMENTS AS REVIEWED FROM
 PREVIOUS REVIEW.
 PLEASE SEE FIRE REVIEW AND BUILDING REVIEW COMMENTS
 WITH RESPECT TO THE FIRE SPRINKLERS AS THE BASE
 BUILDING PLANS ARE REQUIRED TO SHOW COMPLIANCE AND
 STATUTORY REQUIREMENTS AS WELL AS THE FBC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS OR DESIGN.