Plan Review Notes
Plan Review Notes For Permit 06110349
Permit Number 06110349
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-16 16:19:25DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A-4 INDICATES NO PLUMBING FIXTURES. THE PLANS DO
 NOT INDICATE THAT THIS WILL BE A SHELL PERMIT ONLY, NOR
 IS IT INDICATED IN ANY DESCRIPTION OF WORK ON THE
 SUBMITTAL SHEET OR THE PERMIT APPLICATION. SINCE THIS
 IS A PLAN REVIEW ONLY, I WILL ASSUME THAT IT IS A SHELL
 ONLY AND REVIEW IT AS SUCH. ALL MINIMUM FACILITIES WILL
 BE REQUIRED AT TENANT BUILDOUT. TABLES 1004.1.2 &
 403.1. PLEASE INDICATE IF THIS IS INCORRECT.
  
 2. SHT A-5 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. IN THE CALCULATIONS SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS. THESE
 CALCULATIONS ARE REQUIRED FOR THE LOWER ROOFS ALSO.
 INDICATE THE ELEVATIONS FOR THE ROOF, HIGH END AND LOW
 END, TO VERIFY PARAPET WALL CONTRIBUTION.
  
 3. SHTS A-5 & P3.3.1. WITH THE SLOPE OF THE ROOF AS
 INDICATED ON SHT A-5, EXPLAIN HOW ALL ROOF DRAINS SHOW
 THE SAME SQUARE FOOTAGE, (18930SF), DRAINING THROUGH
 EACH DRAIN. ALSO THE ROOF DRAINS ON THE END AREAS OF
 THE BUILDING HAVE EXTRA PARAPET WALL SQUARE FOOTAGE
 THAT DOES NOT CONTRIBUTE TO THE INTERNAL SECTIONS OF
 THE ROOF.
  
 4. SHT A-8 DETAILS 1/A-8 & 3/A-8 BOTH SCALE OUT TO
 APPROXAMATELY 2'9" FROM THE ROOF TO THE TOP OF THE
 PARAPET. PLEASE CLARIFY AS THE ROOF PLAN INDICATES
 1/4"/FT SLOPE @ 150' AND THE PARAPET ON THE LOW END
 SHOULD BE APPROXAMATLY 4' HIGHER WITH BOTH PARAPETS
 BEING 33'-0" AFF.
  
 5. SUBMIT STORM RISER DIAGRAMS SHOWING ALL PIPE SIZES &
 OFFSETS. SECTION 106.3.5.1.3.ARE THE RISER DIAGRAMS
 TO BE PIPED TO THE CATCH BASINS INDIVIDUALLY, OR TO BE
 TIED TOGETHER PRIOR TO THE CATCH BASINS? IF TIED
 TOGETHER, SIZING SHALL BE PER TABLE 1106.3.
  
 6. NO INDICATION OF VENTING IS SHOWN. PLEASE INDICATE
 IF VENTS RUN THRU THE ROOF WILL BE INSTALLED UNDER THE
 SHELL PERMIT, OR WITH THE TENANT BUILDOUT
 PERMIT/PERMITS. SECTION 106.1.1.
  
 7. SHT P5.1 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE OF THE BUILDING. SECTION 608.13.2. PLEASE
 INDICATE ON THE WATER RISER DIAGRAM OR THE PLUMBING
 FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]